| 2020-12-04 09:01:24 | 12/04/20 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIRD REQUEST, PLEASE PROVIDE DETAIL FOR THE WATER |
| | HEATER, HOW IT IS GOING TO DRAIN OUTSIDE, AND THE |
| | METHOD WHICH WILL BE USED TO PREVENT THE RODENT FROM |
| | ENTERING THROUGH THAT DRAIN PER THE 2017 FBC R 2801.6.2 |
| | AND 2017 FBC R 2606.1. |
| | |
| | 2. THRID REQUEST, PLEASE PROVIDE THE SIGNATURE OF ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA THAT SHALL BEAR THE PRINTED NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE INCORPORATE THE ISOMETRIC DRAWING OF THE |
| | PLUMBING SANITARY AND HEATER DETAILS ON A PAGE AND |
| | LABEL P-1 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |