| 2020-10-14 12:18:05 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100383 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE DUCT SIZES ON THE MECHANICAL DRAWING. |
| | FBC RES M1601.1 |
| | |
| | 2) PLEASE SHOW THE BATH EXHAUST FANS ON THE MECHANICAL |
| | DRAWING AND SHOW THE DUCT TERMINATION. FBC RES TABLE |
| | M1507.4 |
| | |
| | 3) PLEASE SHOW THE DRYER DUCT AND THE DUCT TERMINATION |
| | LOCATION. FBC RES M1502 |
| | |
| | 4) IT APPEARS THE AHU?S LOCATION IS IN THE ATTIC. |
| | PLEASE SHOW THE ATTIC ACCESS AND SIZE OF ACCESS ON THE |
| | MECHANICAL DRAWING. FBC RES M1305.1.3 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |