| 2020-10-09 16:50:17 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100372 |
| | 10/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 2751 S |
| | FLAGLER DR. INDICATES A 120,000 BTUH GAS RANGE ISSUED |
| | UNDER PERMIT- 06061405. PLEASE PROVIDE A COMPLETE RISER |
| | DRAWING THAT INCLUDES THE BRANCH LINE TO THE RANGE, THE |
| | TOTAL LENGTH OF THE BRANCH, THE TOTAL DEVELOPED LENGTH |
| | OF THE SYSTEM FROM THE METER TO THE MOST REMOTE OUTLET, |
| | AND THE TOTAL BTUH LOAD OF THE SYSTEM - REFER TO |
| | SECTIONS G2412.3, G2412.4, G2413.1, & G2413.2 FBC RES. |
| | FUEL GAS. |
| | |
| | A) THE SUBMITTED WH SPECS INDICATE 3.5- 10.5 IN. W.C. |
| | INPUT PRESSURE. SHOW THE DELIVERY PRESSURE AT THE |
| | METER, THE LOCATION OF THE LOW PRESSURE REGULATOR, THE |
| | REGULATOR OUTPUT PRESSURE, AND THE REQUIRED PIPE UNIONS |
| | WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- SECTIONS |
| | G2421.1 & G2421.2. |
| | |
| | B) SUBMIT HIGHLIGHTED OR MARKED UP TO SHOW THE SELECTED |
| | MODEL, THE MAX INLET AND OUTLET SIZE AND PRESSURES, AND |
| | ORIFICE SIZE. THE SPECS CAN BE DEFERRED AND BE ONSITE |
| | FOR INSPECTION. |
| | |
| | 2) PROVIDE A PLAN SHOWING THE INTERIOR OR EXTERIOR |
| | LOCATION OF THE NEW WATER HEATER. IF INSTALLED ON THE |
| | EXTERIOR SHOW THE REQUIRED CLEARANCES PER THE |
| | MANUFACTURER'S SPECIFICATIONS, CLEARANCES FOR SERVICE |
| | AND MAINTENANCE, AND VENTING CLEARANCES TO OPERABLE |
| | OPENINGS INTO THE BUILDING- SECTION G2448.1 AND |
| | G2427.1. |
| | |
| | 3) IF INSTALLED ON THE INTERIOR PROVIDE COMBUSTION AIR |
| | AND VENTING PLANS- SECTIONS G2407.1 & G2427.1 |
| | |
| | 4) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |