2020-12-30 07:52:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100364
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE UNIT ABOUT THE GARAGE AND THE UNIT
 SERVING BOTH FLOORS OF THE MAIN HOUSE. THE ORIGINAL
 APPROVED DRAWING INDICATES 2 3-TON UNITS FOR THE MAIN
 HOUSE. FBC EC R403.7
  
 2) PLEASE SHOW THE CONDENSATE DISPOSAL. FBC RES M1411.3
  
 3) PLEASE PROVIDE ENERGY SUBMITTAL FOR THE GARAGE. FBC
 EC 101.5.1.1.2
  
 4) PLEASE SHOW HOW THE CONDENSING UNITS WILL BE
 ANCHORED. FBC RES M1307.2
  
 5) PLEASE PROVIDE CFM?S OF THE HOOD AND THE REQUIRED
 CFM OF THE STOVE. FBC RES M1503.4
  
 6) PLEASE SHOW THE RETURN AIR PATH TO THE AHU IN THE
 MECHANICAL CLOSET, WHAT TYPE OF DOOR IS LOCATED AT THE
 CLOSET OPENING? FBC RES M1602.3
  
 7) SECOND FLOOR BATHROOM WILL NEED TO SHOW AN EXHAUST
 FAN IN THE SHOWER AREA. FBC RES TABLE M1507.4
  
 8) PLEASE PROVIDE A TITLE BLOCK ON THE DRAWING, THE
 DESIGNER OF DRAWING MUST PRINT AND SIGN THE DRAWING.
 FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  