Plan Review Notes
Plan Review Notes For Permit 20100363
Permit Number 20100363
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-05 05:17:541) THE ADDRESS ON THE PERMIT APPLICATION IS STILL
 INCORRECT. THE PLANS NOTE "7038 OKEECHOBEE BLVD." AND
 THE PERMIT APPLICATION NOTES THE ADDRESS AS 7032
 OKEECHOBEE BLVD. SUBMIT A CORRECTED PERMIT APPLICATION
 WITH THE CORRECT ADDRESS WWHICCH IS 7038 OKEECHOBEE
 BLVD. WPB AMEND. TO FBC SEC. 105.3.
 2) THE PLUMBING PLANS SHALL BE DIGITALLY SIGNED AND
 SEALED IN ACCORDANCE WITH FL. ADMIN. CODE RULE
 61G1-16.005 (ARCHITECTS) AND 61G15-23.004, 61G15-23.005
 (ENGINEERS).
 3) THE DISHWASHER IS SHOWN AS ITEM D-5 ON SHT.K1-01 AND
 LISTED AS ITEM D-5 ON SHT. SHT.K1-02 BUT LISTED AS G-7
 ON SHT.P2-01 AND P4-01. ITEM D-5 IS NOT LISTED ON THE
 KITCHEN EQUIPMMENT SCHEDULE ON SHT.P2-01. SHT.K1-02
 LISTS ITEM G-7 AS A SPARE.CLARIFY.
 4) SHT.P2-01 - THE DISHWASHER APPEARS TO BE LOCATED IN
 FRONT A FUTURE LOCATION OF A 200 AMP ELECTRICAL PANEL.
 PLEASE REVIEW AS THIS COULD BE A FUTURE ELECTRICAL CODE
 VIOLATION FOR WORKING CLEARANCES FOR THE ELECTRIC
 PANEL.
 5) SHT. K1-01 - ITEM B8 HAS AN ARROW POINTING TO AN
 OPEN SPACE. NO ITEM IS SHOWN. ITEM B9 IS NOT SHOWN ON
 THE FLOOR PLAN. CLARIFY.
 6) SHT.P5-01 - THE 3- COMP WAREWASH SINK DETAIL APPEARS
 TO SHOW TEMPERED WATER TO THE SINK.THE SINK SHALL BE
 EQUIPPED WITH HOT WATER PER FBC-PLUMBING SEC.607.1.
 7) SHT. P5-01 - WATER HETER DETAILS REFER TO SHT P1-01
 - THIS SHEET IS NOT LISTED IN THE NAMING CONVENTIONS OF
 THE UPLOADED PLANS.THIS SHEET IS LISTED AS P0-01.
 PLEASE CORRECT.
 8) HOT WATER SHALL BE SUPPLIED TO THE HAND SINKS IN THE
 FOOD PREP AREA PER FBC-PLUMBING SEC. 607.1.
 9) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS
 - THE CALCULATIONS SHOW 50 SEATS BUT DOES NOT APPEAR TO
 INCLUDE THE SEATING IN THE DINING BOOTHS OPPOSITE THE
 SEATS. THESE SEATS MUST BE INCLUDED IN THE CALCULATIONS
 AND ALSO IN THE TOTAL OCCUPANT LOAD SHOWN ON SHT.G1-01.
 10) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS
 - THE CALCULATIONS SHOW THE NUMBER OF HOURS OPEN AS 1.5
 LISTED UNDER ITEM #3 AND SHOWN AS 12 HOURS IN THE
 EQUATION. CLARIFY.
 11) IN WORKING THE GREASE INTERCEPTOR EQUATION AS
 LISTED IN FL. ADMIN. CODE RULE 64E-6, MY CALCULATIONS
 SHOW 750 GALLONS. THE MINIMUM VOLUME SHALL BE 750
 GALLONS. FL. ADMIN. CODE RULE 64E-6.013 (7) (D).
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW