| 2021-02-05 05:17:54 | 1) THE ADDRESS ON THE PERMIT APPLICATION IS STILL |
| | INCORRECT. THE PLANS NOTE "7038 OKEECHOBEE BLVD." AND |
| | THE PERMIT APPLICATION NOTES THE ADDRESS AS 7032 |
| | OKEECHOBEE BLVD. SUBMIT A CORRECTED PERMIT APPLICATION |
| | WITH THE CORRECT ADDRESS WWHICCH IS 7038 OKEECHOBEE |
| | BLVD. WPB AMEND. TO FBC SEC. 105.3. |
| | 2) THE PLUMBING PLANS SHALL BE DIGITALLY SIGNED AND |
| | SEALED IN ACCORDANCE WITH FL. ADMIN. CODE RULE |
| | 61G1-16.005 (ARCHITECTS) AND 61G15-23.004, 61G15-23.005 |
| | (ENGINEERS). |
| | 3) THE DISHWASHER IS SHOWN AS ITEM D-5 ON SHT.K1-01 AND |
| | LISTED AS ITEM D-5 ON SHT. SHT.K1-02 BUT LISTED AS G-7 |
| | ON SHT.P2-01 AND P4-01. ITEM D-5 IS NOT LISTED ON THE |
| | KITCHEN EQUIPMMENT SCHEDULE ON SHT.P2-01. SHT.K1-02 |
| | LISTS ITEM G-7 AS A SPARE.CLARIFY. |
| | 4) SHT.P2-01 - THE DISHWASHER APPEARS TO BE LOCATED IN |
| | FRONT A FUTURE LOCATION OF A 200 AMP ELECTRICAL PANEL. |
| | PLEASE REVIEW AS THIS COULD BE A FUTURE ELECTRICAL CODE |
| | VIOLATION FOR WORKING CLEARANCES FOR THE ELECTRIC |
| | PANEL. |
| | 5) SHT. K1-01 - ITEM B8 HAS AN ARROW POINTING TO AN |
| | OPEN SPACE. NO ITEM IS SHOWN. ITEM B9 IS NOT SHOWN ON |
| | THE FLOOR PLAN. CLARIFY. |
| | 6) SHT.P5-01 - THE 3- COMP WAREWASH SINK DETAIL APPEARS |
| | TO SHOW TEMPERED WATER TO THE SINK.THE SINK SHALL BE |
| | EQUIPPED WITH HOT WATER PER FBC-PLUMBING SEC.607.1. |
| | 7) SHT. P5-01 - WATER HETER DETAILS REFER TO SHT P1-01 |
| | - THIS SHEET IS NOT LISTED IN THE NAMING CONVENTIONS OF |
| | THE UPLOADED PLANS.THIS SHEET IS LISTED AS P0-01. |
| | PLEASE CORRECT. |
| | 8) HOT WATER SHALL BE SUPPLIED TO THE HAND SINKS IN THE |
| | FOOD PREP AREA PER FBC-PLUMBING SEC. 607.1. |
| | 9) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS |
| | - THE CALCULATIONS SHOW 50 SEATS BUT DOES NOT APPEAR TO |
| | INCLUDE THE SEATING IN THE DINING BOOTHS OPPOSITE THE |
| | SEATS. THESE SEATS MUST BE INCLUDED IN THE CALCULATIONS |
| | AND ALSO IN THE TOTAL OCCUPANT LOAD SHOWN ON SHT.G1-01. |
| | 10) SHT. P2-01 - GREASE INTERCEPTOR SIZING CALCULATIONS |
| | - THE CALCULATIONS SHOW THE NUMBER OF HOURS OPEN AS 1.5 |
| | LISTED UNDER ITEM #3 AND SHOWN AS 12 HOURS IN THE |
| | EQUATION. CLARIFY. |
| | 11) IN WORKING THE GREASE INTERCEPTOR EQUATION AS |
| | LISTED IN FL. ADMIN. CODE RULE 64E-6, MY CALCULATIONS |
| | SHOW 750 GALLONS. THE MINIMUM VOLUME SHALL BE 750 |
| | GALLONS. FL. ADMIN. CODE RULE 64E-6.013 (7) (D). |
| | |
| | |