| 2020-11-13 11:56:56 | 1) THIS PLAN SHOWS THE ADDRESS OF THE SPACE AS 7000 |
| | OKEECHOBEE BLVD. BUT PERMIT APPLICATION # 20100804 |
| | SHOWS THE ADDRESS FOR THIS SAME SPACE AS 7038 |
| | OKEECHOBEE BLVD.PROVIDE THE CORRECT ADDRESS AND BAY |
| | SPACE NUMBER FOR THIS SPACE.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 2) SHT. G1-01 NOTES THE SQUARE FOOTAGE OF THIS SPACE AS |
| | 1846 SQUARE FEET WITH 64 OCUPANTS AND PERMIT |
| | APPLICATION #20100804 SHOWS THE SQUARE FOOTAGE FOR THIS |
| | SPACE AS 2000 SQUARE FEET WITH 45 OCCUPANTS AND THE |
| | ORIGINAL SHELL PERMIT #19090177 SHOWS THE SQUARE |
| | FOOTAGE FOR THIS SAME SPACE AS 1383 SQUARE FEET. |
| | CLARIFY. |
| | 3) SHT. G1-01 - PLUMBING SYSTEMS TABLE - CALLS OUT THE |
| | 2020 FLORIDA PLUMBING CODE. THE CODE IN EFFECT IS THE |
| | 2017 EDITION OF THE FLORIDA PLUMBING CODE. REVISE THE |
| | NOTE. |
| | 4) G1-03 - ACCESSIBILITY NOTES - NOTE #25 - THE TOILET |
| | PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 INCHES |
| | AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. REVISE THE |
| | NOTE. FBC-ACCESS. SEC.604.9.6. |
| | 5) . A2-10 - KEYNOTES - THE PLANS SHOW A KEYNOTE #8 AT |
| | THE MOP SINK BUT THERE IS NO KEYNOTE #8 LISTED IN THE |
| | KEYNOTES. THIS APPEARS TO BE A TYPO.CLAIFY. |
| | 6) SHT. A5-10 - DETAIL #6 - KNEE CLEARANCE UNDER THE |
| | LAVATORY SHALL BE 8 INCHES DEEP MINIMUM AT 27 INCHES |
| | ABOVE THE FINISH FLOOR. SHOW THIS ON THE PLANS. |
| | FBC-ACCESS. SC. 306.3.3. |
| | 7) INDICATE ON THE PLANS IF THERE WILL BE ANY OUTDOOR |
| | SEATING. IF SO, THESE SEATS MUST BE ADDED TO THE TOTAL |
| | OCCUPANT LOAD WHICH MAY INCREASE THE REQUIRED PLUMBING |
| | FIXTURE COUNT. |
| | 8)SHT. A5-10 - THE PLANS SHOW THE GRAB BARS MEASURED TO |
| | THE CENTERLINE OF THE BAR. GRAB BARS SHALL BE MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE PER FBC-ACCESS. |
| | SEC.609.4. |
| | 9)SHT.A5-10 - THE PLAN SHOWS GRAB BARS INSTALLED IN THE |
| | VERTICAL POSITION. FBC-ACCESS. SEC. 609.4 REQUIRES GRAB |
| | BARS TO BE INSTALLED IN A HORIZONTAL POSITION. THERE IS |
| | NO EXCEPTION ALLOWING GRAB BARS TO BE INSTALLED IN A |
| | VERTICAL POSITION. |
| | 10) SHT. A2-11 - SHOW THE INSIDE CLEAR DIMENSIONS OF |
| | THE TOILET ROOMS ( LENGTH X WIDTH). |
| | 11) SHOW THE DIMENSIONS (L X W) OF THE CLEAR FLOOR |
| | SPACES FOR THE PLUMBING FIXTURES IN THE TOILET |
| | ROOM.COMPLY WITH FBC-ACCESS. SECS.604.3 & 606.2. |
| | 12) SHT. A5- DETAIL #6 - THE HEIGHT OF THE TOILET |
| | APPEARS TO BE MEASURED TO THE TOP OF THE TOILET BOWL. |
| | THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE SEAT PER |
| | FBC-ACCESS. SEC.604.4. |
| | 13) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE |
| | WATER FILTRATION SYSTEM. FBC-PLUMBING SEC.608.3, TABLEE |
| | 608.1. |
| | 14) SUBMIT DETAILS ON THE WATER FILTRATION SYSTEM. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 15) SHT. K1-01 - SHOW THE LOCATION OF THE DISHWASHER ON |
| | THE PLANS (ITEM D5). |
| | 16) P0 - 01 - MATERIALS AND PERFORMANCE - NOTE #9 - |
| | PIPE SLEEVES SHALL BE TWO SIZES GREATER THAN THE PIPE. |
| | FBC-PLUMBING SEC. 305.3. NOTE: THE SHEET SHOULD BE |
| | NAMED AS P1-01, NOT P0-01.. |
| | 17) SHT. P2-01 - THE DISHWASHER (ITEM G7) IS NOT LISTED |
| | ON THE KITCHEN EQUIPMENT SCHEDULE ON SHT. K1-01 OR |
| | K1-02. CLARIFY. |
| | 18) SHT.P2-01 - KEYNOTE #4 - CONDENSATE SHALL NOT BE |
| | DISCHARGED TO THE SANITARY OR GREASE WASTE SYSTEM. |
| | FBC-PLUMBING SEC.1003.2, CITY OF WPB CODE OF ORDINANCES |
| | CHAPT. 90, ART.III, SEC.90-126 (B)(5). |
| | 19) SHT. P3-01 - KEYNOTE #7 REFERS TO AN EXISTING 1 |
| | INCH WATER LINE BUT TABLE TO CALCULATE WATER FIXTURE |
| | UNITS CALLS OUT A 1 1/2 INCH PIPE SIZE.CLARIFY. |
| | 20) SHT. P4-01 - SIZE ALL OF THE VENTS AND DRAIN LINES |
| | ON THE SANITARY RISER. COMPLY WITH FBC-PLUMBING SEC.906 |
| | & TABLE 906.1. |
| | 21) SHT. P4-01 - IDENTIFY THE HOT & COLD WATER DROPS O |
| | THE WATER HEATER ON THE WATER RISER AND LABEL THE |
| | EXISTING WATER LINE COMING INTO THE BUILDING AS SUCH. |
| | 22) SHT. P4-01 - THE GREASE WASTE RISER SHOWS FIXTURE |
| | D5. THIS FIXTURE IS NOT LISTED ON ANY FIXTURE SCHEDULE. |
| | CLARIFY. |
| | 23) SHT. P4-01 - THE HOT WATERFOR FIXTURE H1.1 APPEARS |
| | TO BE CONNETED TO THE RECIRCULATION LINE AND NOT THE |
| | HOT WATER LINE. CLARIFY. |
| | 24) SHT. P5-01 - 3 COMPARTMENT SINK DETAIL - EACH WELL |
| | OF A MULTIPLE - COMPARTMENT SINK SHALL DISCHARGE |
| | INDEPENDENTLY TO A WASTE RECEPTOR.FBC-PLUMBING |
| | SEC.802.1.1. |
| | 25) HOT WATER SHALL B SUPPLIED TO ALL SINKS IN THE FOOD |
| | PREP AREA AND TO THE MOP SINK. FBC-PLUMMBING SEC.607.1. |
| | 26) THERMOSTATIC MIXING VALVES SHALL OMPLY WITH ASSE |
| | 1070. FFBC-PLUMBING SEC. 607.1.2. |
| | 27) SHT. P5-01 - SHOW THE SIZE OF THE EXPANSION TANL ON |
| | THE WATER HEATER DETAIL. |
| | 28) PROVIDE A CLEAR DETAIL OF THE METHOD OF SECURING |
| | THE WATER HEATER. THE SUPPLIED DETAILS ARE UNCLEAR.HOW |
| | IS THE EMT WITH FLATTENED EDGES BEING USED? THE PLAN |
| | SHOWS AN 8 INCH MINIMUM AND 24 INCH MAXIMUM FOR |
| | SOMETHING. THE DETAILS SRE VAGUE. CLARIFY.FBC-PLUMBING |
| | SEC. 308.4. |
| | 29) THE WATER HEATER APPEARS TO BE LOCATED ABOVE THE |
| | MOP SINK.PROVIDE COMPLETE DETAILS FOR THE |
| | SHELF/PLATFORM, TYPE AND SIZE OF CONNECTIONS TO THE |
| | SHELF/PLATFORM AND TO THE BUILDING STRUCTURE, PROVIDE |
| | CLEARANCES FOR MAINTENANCE AND REPLACEMENT IN |
| | ACCORDANCE WITH FBC-PLUMBING SEC.502.5. |
| | 30) SHT. P5-01 - THERE IS A NOTE AT THE WATER HEATER |
| | DETAIL THAT REFERS TO SHT. MPE-02. THERE IS NO SUCH |
| | DRAWING IN THIS SUBMITTAL. CLARIFY. |
| | 31) SIZE ALL SECTIONS OF THE WATER RISER. WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 32) SUBMIT SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTOR. CALCULATIONS WERE NOT SUBMITTED UNDER THE |
| | SHELL PERMIT #19090177. FBC-PLUMBING SEC. 1003.2. |
| | |