Plan Review Notes
Plan Review Notes For Permit 20100363
Permit Number 20100363
Review Stop P
Sequence Number 1
Notes
Date Text
2020-11-13 11:56:561) THIS PLAN SHOWS THE ADDRESS OF THE SPACE AS 7000
 OKEECHOBEE BLVD. BUT PERMIT APPLICATION # 20100804
 SHOWS THE ADDRESS FOR THIS SAME SPACE AS 7038
 OKEECHOBEE BLVD.PROVIDE THE CORRECT ADDRESS AND BAY
 SPACE NUMBER FOR THIS SPACE.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SHT. G1-01 NOTES THE SQUARE FOOTAGE OF THIS SPACE AS
 1846 SQUARE FEET WITH 64 OCUPANTS AND PERMIT
 APPLICATION #20100804 SHOWS THE SQUARE FOOTAGE FOR THIS
 SPACE AS 2000 SQUARE FEET WITH 45 OCCUPANTS AND THE
 ORIGINAL SHELL PERMIT #19090177 SHOWS THE SQUARE
 FOOTAGE FOR THIS SAME SPACE AS 1383 SQUARE FEET.
 CLARIFY.
 3) SHT. G1-01 - PLUMBING SYSTEMS TABLE - CALLS OUT THE
 2020 FLORIDA PLUMBING CODE. THE CODE IN EFFECT IS THE
 2017 EDITION OF THE FLORIDA PLUMBING CODE. REVISE THE
 NOTE.
 4) G1-03 - ACCESSIBILITY NOTES - NOTE #25 - THE TOILET
 PAPER DISPENSER SHALL BE LOCATED A MINIMUM OF 7 INCHES
 AND A MAXIMUM OF 9 INCHES IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. REVISE THE
 NOTE. FBC-ACCESS. SEC.604.9.6.
 5) . A2-10 - KEYNOTES - THE PLANS SHOW A KEYNOTE #8 AT
 THE MOP SINK BUT THERE IS NO KEYNOTE #8 LISTED IN THE
 KEYNOTES. THIS APPEARS TO BE A TYPO.CLAIFY.
 6) SHT. A5-10 - DETAIL #6 - KNEE CLEARANCE UNDER THE
 LAVATORY SHALL BE 8 INCHES DEEP MINIMUM AT 27 INCHES
 ABOVE THE FINISH FLOOR. SHOW THIS ON THE PLANS.
 FBC-ACCESS. SC. 306.3.3.
 7) INDICATE ON THE PLANS IF THERE WILL BE ANY OUTDOOR
 SEATING. IF SO, THESE SEATS MUST BE ADDED TO THE TOTAL
 OCCUPANT LOAD WHICH MAY INCREASE THE REQUIRED PLUMBING
 FIXTURE COUNT.
 8)SHT. A5-10 - THE PLANS SHOW THE GRAB BARS MEASURED TO
 THE CENTERLINE OF THE BAR. GRAB BARS SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE PER FBC-ACCESS.
 SEC.609.4.
 9)SHT.A5-10 - THE PLAN SHOWS GRAB BARS INSTALLED IN THE
 VERTICAL POSITION. FBC-ACCESS. SEC. 609.4 REQUIRES GRAB
 BARS TO BE INSTALLED IN A HORIZONTAL POSITION. THERE IS
 NO EXCEPTION ALLOWING GRAB BARS TO BE INSTALLED IN A
 VERTICAL POSITION.
 10) SHT. A2-11 - SHOW THE INSIDE CLEAR DIMENSIONS OF
 THE TOILET ROOMS ( LENGTH X WIDTH).
 11) SHOW THE DIMENSIONS (L X W) OF THE CLEAR FLOOR
 SPACES FOR THE PLUMBING FIXTURES IN THE TOILET
 ROOM.COMPLY WITH FBC-ACCESS. SECS.604.3 & 606.2.
 12) SHT. A5- DETAIL #6 - THE HEIGHT OF THE TOILET
 APPEARS TO BE MEASURED TO THE TOP OF THE TOILET BOWL.
 THE HEIGHT SHALL BE MEASURED TO THE TOP OF THE SEAT PER
 FBC-ACCESS. SEC.604.4.
 13) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 WATER FILTRATION SYSTEM. FBC-PLUMBING SEC.608.3, TABLEE
 608.1.
 14) SUBMIT DETAILS ON THE WATER FILTRATION SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 15) SHT. K1-01 - SHOW THE LOCATION OF THE DISHWASHER ON
 THE PLANS (ITEM D5).
 16) P0 - 01 - MATERIALS AND PERFORMANCE - NOTE #9 -
 PIPE SLEEVES SHALL BE TWO SIZES GREATER THAN THE PIPE.
 FBC-PLUMBING SEC. 305.3. NOTE: THE SHEET SHOULD BE
 NAMED AS P1-01, NOT P0-01..
 17) SHT. P2-01 - THE DISHWASHER (ITEM G7) IS NOT LISTED
 ON THE KITCHEN EQUIPMENT SCHEDULE ON SHT. K1-01 OR
 K1-02. CLARIFY.
 18) SHT.P2-01 - KEYNOTE #4 - CONDENSATE SHALL NOT BE
 DISCHARGED TO THE SANITARY OR GREASE WASTE SYSTEM.
 FBC-PLUMBING SEC.1003.2, CITY OF WPB CODE OF ORDINANCES
 CHAPT. 90, ART.III, SEC.90-126 (B)(5).
 19) SHT. P3-01 - KEYNOTE #7 REFERS TO AN EXISTING 1
 INCH WATER LINE BUT TABLE TO CALCULATE WATER FIXTURE
 UNITS CALLS OUT A 1 1/2 INCH PIPE SIZE.CLARIFY.
 20) SHT. P4-01 - SIZE ALL OF THE VENTS AND DRAIN LINES
 ON THE SANITARY RISER. COMPLY WITH FBC-PLUMBING SEC.906
 & TABLE 906.1.
 21) SHT. P4-01 - IDENTIFY THE HOT & COLD WATER DROPS O
 THE WATER HEATER ON THE WATER RISER AND LABEL THE
 EXISTING WATER LINE COMING INTO THE BUILDING AS SUCH.
 22) SHT. P4-01 - THE GREASE WASTE RISER SHOWS FIXTURE
 D5. THIS FIXTURE IS NOT LISTED ON ANY FIXTURE SCHEDULE.
 CLARIFY.
 23) SHT. P4-01 - THE HOT WATERFOR FIXTURE H1.1 APPEARS
 TO BE CONNETED TO THE RECIRCULATION LINE AND NOT THE
 HOT WATER LINE. CLARIFY.
 24) SHT. P5-01 - 3 COMPARTMENT SINK DETAIL - EACH WELL
 OF A MULTIPLE - COMPARTMENT SINK SHALL DISCHARGE
 INDEPENDENTLY TO A WASTE RECEPTOR.FBC-PLUMBING
 SEC.802.1.1.
 25) HOT WATER SHALL B SUPPLIED TO ALL SINKS IN THE FOOD
 PREP AREA AND TO THE MOP SINK. FBC-PLUMMBING SEC.607.1.
 26) THERMOSTATIC MIXING VALVES SHALL OMPLY WITH ASSE
 1070. FFBC-PLUMBING SEC. 607.1.2.
 27) SHT. P5-01 - SHOW THE SIZE OF THE EXPANSION TANL ON
 THE WATER HEATER DETAIL.
 28) PROVIDE A CLEAR DETAIL OF THE METHOD OF SECURING
 THE WATER HEATER. THE SUPPLIED DETAILS ARE UNCLEAR.HOW
 IS THE EMT WITH FLATTENED EDGES BEING USED? THE PLAN
 SHOWS AN 8 INCH MINIMUM AND 24 INCH MAXIMUM FOR
 SOMETHING. THE DETAILS SRE VAGUE. CLARIFY.FBC-PLUMBING
 SEC. 308.4.
 29) THE WATER HEATER APPEARS TO BE LOCATED ABOVE THE
 MOP SINK.PROVIDE COMPLETE DETAILS FOR THE
 SHELF/PLATFORM, TYPE AND SIZE OF CONNECTIONS TO THE
 SHELF/PLATFORM AND TO THE BUILDING STRUCTURE, PROVIDE
 CLEARANCES FOR MAINTENANCE AND REPLACEMENT IN
 ACCORDANCE WITH FBC-PLUMBING SEC.502.5.
 30) SHT. P5-01 - THERE IS A NOTE AT THE WATER HEATER
 DETAIL THAT REFERS TO SHT. MPE-02. THERE IS NO SUCH
 DRAWING IN THIS SUBMITTAL. CLARIFY.
 31) SIZE ALL SECTIONS OF THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 32) SUBMIT SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTOR. CALCULATIONS WERE NOT SUBMITTED UNDER THE
 SHELL PERMIT #19090177. FBC-PLUMBING SEC. 1003.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  