Plan Review Notes
Plan Review Notes For Permit 20100363
Permit Number 20100363
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-19 14:40:12CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) ELECTRICAL ROOF PLAN SHOWS CIRCUIT PP 27,29,31 FOR
 RTU#1 SIZED AS 3#8, 1#10 GND (DOES NOT MEET AMPACITY
 REQUIRED) WHILE NOTE 10 SPECIFIES 3#3, 1#8 CONDUCTOR
 WITH 100 A SWITCH. PANEL PP SHOWS THIS CIRCUIT WITH AN
 80 AMPS BREAKER. PLEASE CORRECT WITH PROPER CONDUCTOR
 SIZE AND MAKE INFORMATION CONSISTENT.
 2) ALL COMMERCIAL KITCHEN RECEPTACLES MUST HAVE GFCI
 PROTECTION. DEFINITION OF KITCHEN INCLUDES FOOD
 PREPARATION AREAS. PLEASE PROVIDE GFCI PROTECTION FOR
 RECEPTACLES IN FOOD PREPARATION AREA (PP-59). NEC 100,
 NEC 210.8 (B)(2).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  