Plan Review Notes
Plan Review Notes For Permit 20100363
Permit Number 20100363
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-20 16:23:18WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100367
 ADD: 7000 OKEECHOBEE BLVD. (SUITE: 7038) SUITE NUMBER
 NEEDS TO BE ADDED TO PLAN.
 CONT: TBD/ TO BE DETERMINED
 TEL: ???
 E-MAIL: [email protected] / DAVID NITECKI
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. OCT. 20/2020
 ACTION: DENIED
  
 1) SHEET G1-01 PROJECT INFO & CODE:
 1A) THE KEY PLAN INDICATES THE GREAT GREEK RESTAURANT
 IS TAKING ONLY PART OF BUILDING ADDRESSED AS 7000
 OKEECHOBEE BLVD. WILL NEED A TENANT ADDRESS., SUITE
 NUMBER.
 2017 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 1B) UNDER THE HEADING OF THE CODE MATRIX THE PLANS
 STATE THE CONSTRUCTION TYPE AS III-B. THE PLANS ARE
 SILENT AS IF THE BUILDING IS FIRE SPRINKLERED OR NOT?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 1C) UNDER THE CODE MATRIX INTERIOR FINISHES THE EDITION
 OF THE CODE IS LISTED AS THE 2020 FBC. PLEASE NOTE WE
 ARE CURRENTLY UNDER THE 6TH EDITION OF THE FLORIDA
 BUILDING CODE 2017.
  
 1D) THE NOTE STATES TO MEET ALL REQUIREMENTS OF THE
 AMERICANS DISABILITY ACT, STATE OF FLORIDA CODE AND
 ICC/ANSI 117.1A THE MOST RESTRICTIVE REQUIREMENT SHALL
 GOVERN. PLEASE NOTE THE STATE OF FLORIDA HAS ADOPTED
 THE 2017 FBC-ACCESSIBILITY CODE WHICH HAS BEEN BLESSED
 BY THE DEPARTMENT OF JUSTICE. OUR CODE SECTIONS WILL
 REFERENCE THE 2017 FLORIDA ACCESSIBILITY CODE.
  
 2) THE INTERIOR LIGHTING COMPLIANCE CERTIFICATE
 INDICATE IT IS FOR THE GREAT GREEK. CONSTRUCTION SITE
 LISTED AS:
 2121 VISTA PARKWAY
 WEST PALM BEACH, FL.
 VISTA PARKWAY IS IN PALM BEACH COUNTY, NOT IN THE CITY
 OF WEST PALM BEACH. CORRECT THE ADDRESS.
  
 3) SHEET A5-10:
 3A) PLEASE REVIEW HOW THE HEIGHT OF THE WATER CLOSET
 GRAB BARS ARE DIMENSIONED FOR HEIGHT FROM FINISH FLOOR.
 2017 FBC-ACCESSIBILITY CODE SECTION 609.4 POSITION OF
 GRAB BARS. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL
 POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE
 THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING
 SURFACE, NOT CENTERLINE.
 3B) DETAIL 6 DOES NOT SHOW THE LAVATORY PIPES WITH
 INSULATION. 2017 FBC-ACCESS. CODE SECTION 606.5 EXPOSED
 PIPES AND SURFACES. WATER SUPPLY & DRAINPIPES UNDER
 LAVATORIES AND SINKS SHALL BE INSULATED OR OTHERWISE
 CONFIGURED TO PROTECT AGAINST CONTACT.
 4) THE K1-0 EQ & FURNITURE PLAN:
 4A) THE FURNITURE FLOOR PLAN SHOWS 62 SEATS AND ONLY
 ONE ACCESSIBLE SEAT SYMBOL. 2017 FBC-ACCESS. CODE 226.1
 WHERE DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION
 OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING
 SPACES AND STANDING SPACES AT THE DINING SURFACES SHALL
 COMPLY WITH 902. 62X 0.05= 4 ACCESSIBLE SEATS.
  
 4B) 226.2 DISPERSION. DINING SURFACES ARE REQUIRED TO
 COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE SPACE
 OR FACILITY CONTAINING DINING SURFACES. WILL THERE BE
 ADDITIONAL OUTSIDE SEASONAL SEATING?
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS
  
 4D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 5) THE MECHANICAL ROOF TOP PLAN KEY NOTES:
 5A KEY NOTE 1 STATES FURNISH AND INSTALL ROOFTOP UNITS
 RTU 1 & 2 VERIFY WITH LANDLORD REPRESENTATIVE AND
 STRUCTURAL DRAWINGS. THE ORIGINAL SHELL BUILDING PERMIT
 # 19081537 SHEET 15/63 STATES RTU # 1 & 2 ROOF OPENING
 FRAMING BY OTHERS UNDER SEPARATE PERMIT. THESE PLANS
 ALSO SHOW STEEL BAR JOIST AND METAL B DECKING.
 5A)(1) PROVIDE ADDITIONAL STRUCTURAL PLANS FOR THE
 RE-INFORCEMENT OF BAR JOIST FOR POINT LOADING, PROVIDE
 THE STEEL INFILL FRAMING FOR THE FUTURE RTU?S UNITS.
 PROVIDE ANCHORAGE FOR THE STEEL FRAMING, THE CURB TO
 THE STEEL FRAMING AND THE ANCHORAGE OF THE RTU TO THE
 ROOF CURB.
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
  
  
 5B) KEY NOTE 2 STATES PROVIDE ROOF MOUNTED EXHAUST FANS
 EF 1 & 2 WITH MANUFACTURES APPROVED ROOF CURB. PROVIDE
 ADDITIONAL STRUCTURAL PLANS FOR THE RE-INFORCEMENT OF
 BAR JOIST FOR POINT LOADING, PROVIDE THE STEEL INFILL
 FRAMING FOR THE FUTURE RTU?S UNITS. PROVIDE ANCHORAGE
 FOR THE STEEL FRAMING, THE CURB TO THE STEEL FRAMING
 AND THE ANCHORAGE OF THE RTU TO THE ROOF CURB.
 2017 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 5C) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION FOR FIELD WIELDING, ON THE JOB-SITE
 WIELDING. THIRD PARTY CERTIFICATION WILL BE REQUIRED.
 REPORTS SUBMITTED TO BUILDING INSPECTOR AT TIME OF
 FRAMING INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT
 561-805-6666.
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  