| 2020-11-18 11:50:08 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100351 |
| | 11/18//2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTES. |
| | |
| | 3) FAILED. P2.00: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE |
| | THAT TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070- |
| | SECTION 607.1.2 FBC P. NO PLAN DETAILS OR NOTES |
| | PROVIDED. |
| | |
| | 5) FAILED. P2.00: SHOW THE REQUIRED 36 IN. CLEARANCE |
| | FOR THE NEW STORM DRAIN CLEANOUT AND ACCESS FROM, AND |
| | PERPENDICULAR TO, THE FACE OF THE OPENING TO ANY |
| | OBSTRUCTION- SECTION 708.1.9 FBC P. NO RESPONSE FROM |
| | THE DESIGN PROFESSIONALS AND NO PLAN DETAILS OR NOTES |
| | PROVIDED. |
| | |
| | 7) FAILED. ACCESSIBLE PLUMBING FIXTURE REQUIREMENTS PER |
| | FBC ACC. PROVIDE DRAWINGS AND DETAILS SHOWING: |
| | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 & 609.4. MOUNTING HEIGHTS NOT SHOWN |
| | ON SHEET A0.02 |
| | L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE |
| | BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3. MIRROR |
| | DETAIL NOT SHOWN ON SHEETS A0.02. |
| | |
| | 9) FAILED. AS NOTED IN COMMENT #1 DRINKING FOUNTAINS |
| | ARE REQUIRED FIXTURES AND SHALL BE ACCESSIBLE IN |
| | ACCORDANCE WITH SECTIONS 211.2 & 602.1- 602.6 FBC ACC. |
| | PROVIDE DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO THE |
| | WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 |
| | FBC ACC. B) KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, |
| | SPOUT LOCATIONS- SECTIONS 306, 307, & 602.2. C) |
| | COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. |
| | ACKNOWLEDGED THAT THE DRINKING FOUNTAIN IS NOT |
| | REQUIRED, HOWEVER THE FIXTURE SCHEDULE SPECIFIES A |
| | DRINKING FOUNTAIN WALL BOX. REVISE THE DRAWINGS PER THE |
| | NOTES BELOW: |
| | A) SHOW THE LOCATION OF THE WATER DISPENSER ON THE |
| | FLOOR PLAN. |
| | B) INDICATE THE MAKE AND MODEL OF THE UNIT IN THE |
| | FIXTURE SCHEDULE. |
| | C) PROVIDE PLUMBING PIPING CONNECTION DETAILS. |
| | D) PROVIDE PLAN DETAILS TO SHOW COMPLIANCE WITH FBC ACC |
| | SECTIONS 305- 309: CLEAR FLOOR SPACE APPROACH, KNEE AND |
| | TOE CLEARANCES, PROTRUDING OBJECTS, REACH RANGES, AND |
| | OPERABLE PARTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |