Plan Review Notes
Plan Review Notes For Permit 20100351
Permit Number 20100351
Review Stop P
Sequence Number 2
Notes
Date Text
2020-11-18 11:50:082ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20100351
 11/18//2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES.
  
 3) FAILED. P2.00: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE
 THAT TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070-
 SECTION 607.1.2 FBC P. NO PLAN DETAILS OR NOTES
 PROVIDED.
  
 5) FAILED. P2.00: SHOW THE REQUIRED 36 IN. CLEARANCE
 FOR THE NEW STORM DRAIN CLEANOUT AND ACCESS FROM, AND
 PERPENDICULAR TO, THE FACE OF THE OPENING TO ANY
 OBSTRUCTION- SECTION 708.1.9 FBC P. NO RESPONSE FROM
 THE DESIGN PROFESSIONALS AND NO PLAN DETAILS OR NOTES
 PROVIDED.
  
 7) FAILED. ACCESSIBLE PLUMBING FIXTURE REQUIREMENTS PER
 FBC ACC. PROVIDE DRAWINGS AND DETAILS SHOWING:
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4. MOUNTING HEIGHTS NOT SHOWN
 ON SHEET A0.02
 L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3. MIRROR
 DETAIL NOT SHOWN ON SHEETS A0.02.
  
 9) FAILED. AS NOTED IN COMMENT #1 DRINKING FOUNTAINS
 ARE REQUIRED FIXTURES AND SHALL BE ACCESSIBLE IN
 ACCORDANCE WITH SECTIONS 211.2 & 602.1- 602.6 FBC ACC.
 PROVIDE DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48
 IN. CLEAR FLOOR SPACE FOR A FORWARD APPROACH TO THE
 WHEELCHAIR ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2
 FBC ACC. B) KNEE AND TOE CLEARANCES, SPOUT HEIGHTS,
 SPOUT LOCATIONS- SECTIONS 306, 307, & 602.2. C)
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
 ACKNOWLEDGED THAT THE DRINKING FOUNTAIN IS NOT
 REQUIRED, HOWEVER THE FIXTURE SCHEDULE SPECIFIES A
 DRINKING FOUNTAIN WALL BOX. REVISE THE DRAWINGS PER THE
 NOTES BELOW:
 A) SHOW THE LOCATION OF THE WATER DISPENSER ON THE
 FLOOR PLAN.
 B) INDICATE THE MAKE AND MODEL OF THE UNIT IN THE
 FIXTURE SCHEDULE.
 C) PROVIDE PLUMBING PIPING CONNECTION DETAILS.
 D) PROVIDE PLAN DETAILS TO SHOW COMPLIANCE WITH FBC ACC
 SECTIONS 305- 309: CLEAR FLOOR SPACE APPROACH, KNEE AND
 TOE CLEARANCES, PROTRUDING OBJECTS, REACH RANGES, AND
 OPERABLE PARTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  