Plan Review Notes
Plan Review Notes For Permit 20100351
Permit Number 20100351
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-28 14:55:391ST REVIEW FBC-2017 PLUMBING
 PERMIT- 20100351
 10/28/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A0.01 & P0.00: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3. PROVIDE A
 SCHEDULE ON THE PLAN THAT SHOWS THE NUMBER OF REQUIRED
 AND PROVIDED FIXTURES. PLEASE NOTE THAT REQUIRED
 FIXTURES FOR MERCANTILE OCCUPANCIES INCLUDE DRINKING
 FOUNTAINS AND A SERVICE SINK. REVISE THE PLANS TO SHOW
 THE LOCATIONS OF THE FIXTURES AND PLUMBING PIPING
 DETAILS- SECTION 107.2.1 WPB.
  
 2) P2.00: A FULL OPEN SHUTOFF VALVE SHALL BE LOCATED ON
 THE DISCHARGE SIDE OF THE WATER METER- SECTION 606.1(3)
 FBC P.
  
 3) P2.00: INDICATE HOW TEMPERED WATER WILL BE PROVIDED
 AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE THAT
 TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070-
 SECTION 607.1.2 FBC P.
  
 4) P2.00: SHOW THE LOCATIONS OF WATER HAMMER ARRESTORS
 FOR SUPPLY LINES TO QUICK CLOSING VALVES- SECTION-
 604.9 FBC P.
  
 5) P2.00: SHOW THE REQUIRED 36 IN. CLEARANCE FOR THE
 NEW STORM DRAIN CLEANOUT AND ACCESS FROM, AND
 PERPENDICULAR TO, THE FACE OF THE OPENING TO ANY
 OBSTRUCTION- SECTION 708.1.9 FBC P.
  
 6) P2.00: PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1
 WPB.
  
 7) ACCESSIBLE PLUMBING FIXTURE REQUIREMENTS PER FBC
 ACC. PROVIDE DRAWINGS AND DETAILS SHOWING:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSION FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHTS OF THE FRONT RIM OF THE LAVATORY FROM THE
 FINISHED FLOOR- SECTION 606.3
 G) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 306.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5 & 609.4
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SECTION
 604.6.
 J) LOCATION, CLEARANCE, AND MOUNTING HEIGHT FOR THE
 TOILET PAPER DISPENSER- SECTION 604.7.
 L) HEIGHT OF THE MIRROR FROM THE FINISHED FLOORS TO THE
 BOTTOM OF THE REFLECTIVE SURFACE- SECTION 603.3.
  
 8) SHEET A1.01: THE RESTROOM DOOR SHALL NOT SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY- SECTION-
 603.2.3 FBC ACC. PLEASE SEE EXCEPTION 2.
  
 9) AS NOTED IN COMMENT #1 DRINKING FOUNTAINS ARE
 REQUIRED FIXTURES AND SHALL BE ACCESSIBLE IN ACCORDANCE
 WITH SECTIONS 211.2 & 602.1- 602.6 FBC ACC. PROVIDE
 DRAWINGS AND DETAILS SHOWING: A) THE 30 X 48 IN. CLEAR
 FLOOR SPACE FOR A FORWARD APPROACH TO THE WHEELCHAIR
 ACCESSIBLE DRINKING FOUNTAIN- SECTION 602.2 FBC ACC. B)
 KNEE AND TOE CLEARANCES, SPOUT HEIGHTS, SPOUT
 LOCATIONS- SECTIONS 306, 307, & 602.2. C) COMPLIANCE
 WITH SECTION 307.2 PROTRUSION LIMITS.
  
 10) INDICATE THE TYPE OF WALL FINISHES TO BE INSTALLED
 IN THE RESTROOM AND AT THE MOP SINK LOCATION IN
 ACCORDANCE WITH SECTIONS 310.3 FBC P, AND 1210.2.2 FBC
 B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  