| Plan Review Notes For Permit 20100351 |
| Permit Number |
20100351 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-30 10:48:30 | BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE SIZE OF THE EXISTING EGRESS DOOR | | | FROM THE UNIT. | | | 2) PLEASE SHOW THE RESTROOM WALLS TO COMPLY WITH FBC | | | 1210.2.2WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE | | | SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, | | | HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS | | | THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR | | | STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS | | | SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY | | | MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE). | | | 3) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC | | | CHAPTER 3. | | | 4) WALL TYPE "P1" IS SHOWN ON THE FLOOR PLAN AS THE | | | DEMISING WALL - IN THE WALL SCHEDULE ON THE DRAWING | | | "P1" IS NOT FIRE RATED - IS THIS CORRECT?? | | | 5) PLEASE PROVIDE THE ADA CLEAR FLOOR SPACE SIZES, | | | TURNING RADIUS, ACCESSORY DIMENSIONS FROM FLOOR FINISH, | | | ETC. - FBC ACCESSIBILITY - ( PERHAPS BY PROVIDING AN | | | ADA COMPLIANCE DETAILS PLAN). | | | | | | |
|