Plan Review Notes
Plan Review Notes For Permit 20100351
Permit Number 20100351
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-30 10:48:30BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE SIZE OF THE EXISTING EGRESS DOOR
 FROM THE UNIT.
 2) PLEASE SHOW THE RESTROOM WALLS TO COMPLY WITH FBC
 1210.2.2WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE).
 3) PLEASE SHOW THE OCCUPANCY CLASSIFICATION PER FBC
 CHAPTER 3.
 4) WALL TYPE "P1" IS SHOWN ON THE FLOOR PLAN AS THE
 DEMISING WALL - IN THE WALL SCHEDULE ON THE DRAWING
 "P1" IS NOT FIRE RATED - IS THIS CORRECT??
 5) PLEASE PROVIDE THE ADA CLEAR FLOOR SPACE SIZES,
 TURNING RADIUS, ACCESSORY DIMENSIONS FROM FLOOR FINISH,
 ETC. - FBC ACCESSIBILITY - ( PERHAPS BY PROVIDING AN
 ADA COMPLIANCE DETAILS PLAN).
  
  