| 2020-12-18 07:53:29 | |
| | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100289 |
| | 12/18/20 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | FAIR HOUSING ACT DESIGN MANUAL COMPLIANCE. |
| | |
| | 1) SHEET 1: THE REVISED PLAN IS INDICATING A |
| | SPECIFICATION TYPE B DESIGN FOR THE MASTER BATH, |
| | HOWEVER THE REQUIRED 30X48 IN. CLEAR FLOOR SPACE |
| | DIAGRAM AT THE BATHTUB AND THE REQUIRED 30X48 IN. CLEAR |
| | FLOOR SPACE OUTSIDE THE SWING OF THE DOOR ARE NOT |
| | SHOWN. ALSO REQUIRED ARE THE GRAB BAR BACKING |
| | REINFORCEMENTS LOCATION DIASGRAMS AT THE BATHTUB FOR |
| | GRAB BARS- REFER TO LAYOUTS ON PAGES 7.37 & 7.40. |
| | PLEASE NOTE IN SPECIFICATION B ONLY ONE OF THE TWO |
| | BATHING FIXTURES MUST BE PROVIDED WITH THE REQUIRED |
| | CLEAR FLOOR SPACE- PAGE 7.56. BASED ON THE REVISED PLAN |
| | AND THE CLEAR FLOOR SPACE DIAGRAMS FOR SHOWERS ON PAGES |
| | 7.56- 7.58 THE CLEAR FLOOR SPACE SHOWN AT THE SHOWER |
| | DOES NOT MEET COMPLIANCE. PLEASE REVISE THE PLAN TO |
| | SHOW THE BATHTUB MEETS COMPLIANCE. |
| | |
| | AS PREVIOUSLY NOTED IN THE FIRST REVIEW, AS AN |
| | ALTERNATIVE TO MEETING THE GUIDELINES FOR THE BATH |
| | ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR THE |
| | PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED |
| | AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE |
| | PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE |
| | FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO |
| | REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO |
| | COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE |
| | BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL |
| | TO [email protected] AND I WILL SEND A COPY OF THE FAIR |
| | HOUSING AFFIDAVIT. |
| | |
| | 2) 2ND REQUEST TO SUBMIT A PLUMBING SUB-PERMIT |
| | APPLICATION- SECTION 105.1 WPB. PLEASE NOTE THE |
| | APPLICATION MAY BE SUBMITTED AFTER THE MAIN PERMIT IS |
| | ISSUED, HOWEVER NO PLUMBING WORK SHALL COMMENCE UNTIL |
| | THE SUB- PERMIT IS ISSUED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |