Plan Review Notes
Plan Review Notes For Permit 20100270
Permit Number 20100270
Review Stop B
Sequence Number 2
Notes
Date Text
2020-12-14 12:59:11INTERIOR REPAIRS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 2ND REVIEW
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE LOCATION OF THE REQUIRED SMOKE
 DETECTORS FBC R314.2.2 ALTERATIONS, REPAIRS AND
 ADDITIONS.
 WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1.IN EACH SLEEPING ROOM.
 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
  
 2) IS THE INSULATION BEING REPLACED? IF SO SHOW THE
 INSULATION "R" VALUE - CAN COMPLY WITH FBC ENERGY 402.1
 (R30)
 3) PLEASE SHOW THE SIZE AND LOCATION OF THE ATTIC
 ACCESS TO COMPLY WITH FBC R807 (SHOW THE EXISTING
 LOCATION)