| Plan Review Notes For Permit 20100270 |
| Permit Number |
20100270 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-12-14 12:59:11 | INTERIOR REPAIRS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | 2ND REVIEW | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) PLEASE SHOW THE LOCATION OF THE REQUIRED SMOKE | | | DETECTORS FBC R314.2.2 ALTERATIONS, REPAIRS AND | | | ADDITIONS. | | | WHERE ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHERE ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. R314.3 LOCATION. | | | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING | | | LOCATIONS: | | | 1.IN EACH SLEEPING ROOM. | | | 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE | | | VICINITY OF THE BEDROOMS. | | | | | | 2) IS THE INSULATION BEING REPLACED? IF SO SHOW THE | | | INSULATION "R" VALUE - CAN COMPLY WITH FBC ENERGY 402.1 | | | (R30) | | | 3) PLEASE SHOW THE SIZE AND LOCATION OF THE ATTIC | | | ACCESS TO COMPLY WITH FBC R807 (SHOW THE EXISTING | | | LOCATION) |
|