| 2020-10-07 12:47:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100263 |
| | 10/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 944 |
| | CHURCHILL RD. SHOW A GAS PERMIT #15040162 WAS ISSUED ON |
| | 4/6/2015 FOR GAS LINE INSTALLATION TO A NEW TANKLESS |
| | WATER HEATER AT 150,000 BTUH, AND A NEW DRYER AT 35,000 |
| | BTUH. PLEASE REVISE THE GAS RISER TO SHOW A COMPLETE |
| | PIPING SYSTEM THAT INCLUDES THE NEW GENERATOR AND THE |
| | EXISTING APPLIANCES- SECTIONS G2412.3 & G2412.4 FBC |
| | RES. PLEASE INCLUDE THE TYPE, SIZE, AND LENGTH OF THE |
| | MAIN SUPPLY PIPE FROM THE METER TO THE TEE. |
| | |
| | A) SHOW THE CORRECT TOTAL LOAD AND THE INDIVIDUAL LOADS |
| | OF THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. PLEASE NOTE THE GENERATOR PERMIT- 20090421 SHOWS A |
| | 22 KW GENERATOR AT 327.000 BTUH. |
| | |
| | B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| | G2413.4.2 FBC RES. |
| | |
| | C) SHOW THE LOCATIONS OF SHUT OFF VALVES AND PIPE |
| | UNIONS- SECTIONS G2420.5 & G2422.1.4. |
| | |
| | D) SHOW THE LOCATIONS OF NEW AND EXISTING REGULATORS. |
| | INDICATE THE MAKES AND MODELS OF THE REGULATORS AND |
| | THEIR INLET AND OUTLET PRESSURES- SECTION G2421.1 & |
| | G2421.2. SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING |
| | THE SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, SPRING DATA, AND ORIFICE SIZE. IF CONNECTED |
| | TO RIGID PIPING, PIPE UNIONS ARE REQUIRED WITH 1 FT. OF |
| | EITHER SIDE OF THE REGULATOR- SECTION G2421.2(7). |
| | |
| | E) SHOW THE LOCATIONS OF DRIP LEGS- SECTION G2419.2. |
| | |
| | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT |
| | INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |