| 2020-10-29 21:49:11 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FAULT CURRENT AT FPL TRANSFORMER SECONDARY IS |
| | 21200AMPS PER FAULT CURRENT LETTER. NOTE ON PLAN STATES |
| | ALL EQUIPMENT WILL BE RATED AT 10,000 AIC. PROVIDE |
| | FAULT CURRENT CALCULATION SHOWING FAULT CURRENT RATING |
| | FROM SECONDARY OF TRANSFORMER TO SERVICE ENTRANCE |
| | EQUIPMENT. NEC 110.10 FBC 107.2.1 |
| | |
| | 2. SMOKE/CARBON ALARM IN KITCHEN MUST BE ATLEAST 10' |
| | AWAY FROM NEAREST COOKING APPLIANCE. NEC 110.3B PROVIDE |
| | CORRECTION. |
| | |
| | 3. BALCONIES ON SECOND FLOOR ARE MISSING REQUIRED |
| | RECEPTACLE OUTLETS NEC 210.52E3 |
| | |
| | 4. TAMPERPROOF RECEPTACLES ARE REQUIRED PER NEC 406.12 |
| | PROVIDE CORRECTION. A NOTE ON PLAN WILL SUFFICE. |
| | |
| | 5. NOTE ON RISER DIAGRAM SAYS "1/0 TO GROUND RODS THEN |
| | CW PIPE" BUT DIAGRAM SHOWS #4. PROVIDE CORRECTION. #4 |
| | IS ALL THATS REQUIRED FOR GROUND RODS, CW PIPE, AND |
| | BUILDING STEEL FYI. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |