| 2020-10-27 09:10:53 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100238 |
| | 10/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A210: THE RESTROOM DOOR SHALL NOT SWING INTO |
| | THE CLEAR FLOOR SPACE OF THE LAVATORY- SECTION 603.2.3 |
| | FBC ACC. PLEASE SEE EXCEPTIONS UNDER 603.2.3. |
| | |
| | 2) A210 & P1.1: SHOW THE CLEAR FLOOR SPACE APPROACH |
| | DIAGRAMS AND DIMENSIONS FOR SK 1 & 2- SECTIONS 212.3, |
| | 305.3, & 606.2 FBC ACC. |
| | |
| | 3) A210: IT APPEARS THAT THE STORAGE RM 307 DOOR WILL |
| | SWING INTO THE CLEAR FLOOR SPACE FOR SK-1- SECTION |
| | 603.2.3 FBC ACC. |
| | |
| | 4) A310: SHOW THE CENTERLINE OF THE TOILET PAPER |
| | DISPENSER MEASURED FROM THE FRONT OF THE WATER CLOSET- |
| | SECTION 604.7 FBC ACC. |
| | |
| | 5) P1.1: SHOW A BACKFLOW PREVENTER FOR THE SUPPLY LINE |
| | TO THE ICE MAKER- SECTION 608.3 FBC P. |
| | |
| | 6) P0.1 & P1.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | ICE MAKER AND INDICATE HOW CONDENSATION FROM THE UNIT |
| | WILL BE DISPOSED OF- SECTION 314.2.1 FBC P. |
| | |
| | 7) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |