| Date |
Text |
| 2020-11-05 11:36:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO INDICATION OF A DOOR SCHEDULE INCLUDING |
| | HANDLE TYPE, AND LOCK/LATCH. |
| | |
| | PER NFPA 101, CH 7, MEANS OF EGRESS |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL |
| | BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF |
| | OPERATION AND THAT IS READILY OPERATED UNDER ALL |
| | LIGHTING CONDITIONS. |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE |
| | LOCATED AS FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR |
| | OTHER THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF |
| | WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS |
| | OTHERWISE |
| | SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR |
| | 7.2.1.5.10.6. |
| | |
| | PLEASE PROVIDE DETAILS IN COMPLIANCE WITH THE ABOVE. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF AN INTERIOR EXT SIGN. |
| | |
| | PER NFPA 101, CH 7 |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS. |
| | |
| | PLEASE PROVIDE IF APPLICABLE, PROVIDE JUSTIFICATION IF |
| | NONE INSTALLED. |
| | |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |