| 2020-10-06 17:27:39 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100213 |
| | 10/6/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE REVISED PLANS DO NOT SHOW ANY CHANGES THAT |
| | CORRELATE WITH REVISION 2 WHICH IS LISTED IN THE |
| | REVISION SCHEDULE ON EACH PLAN SHEET- SECTION 107.2.1 |
| | WPB. |
| | |
| | 2) SHEET P101: NEW FLOOR SINKS AND HAND SINKS IN THE |
| | KITCHEN SHALL CONNECT TO THE GREASE WASTE LINE- SECTION |
| | 1003.3.1 FBC P AND SEC.90-126(7) CITY OF WPB CODE OF |
| | ORDINANCES. THE PLAN SHOWS CONNECTIONS INTO THE |
| | SANITARY- PLEASE CORRECT. |
| | |
| | 3) P101, P102, P202, P203: PROVIDE A REVISED PLUMBING |
| | FIXTURE SCHEDULE CORRELATING WITH THE NEW P FIXTURES |
| | SHOWN ON THE PLANS- SECTION 107.2.1 WPB. PLEASE NOTE |
| | THE APPROVED PLAN UNDER PERMIT-17121049 HAD AN |
| | EQUIPMENT SCHEDULE ON SHEET P201. A COMPLETE REVIEW OF |
| | THE PLANS CANNOT BE COMPLETED WITHOUT THE SCHEDULE. |
| | |
| | 4) P101: SUBMIT REVISED CIVIL PLANS SHOWING THE |
| | SANITARY AND GREASE WASTE LINE CONTINUATIONS AND |
| | LOCATION OF THE GREASE INTERCEPTOR- SECTION 107.2.1 |
| | WPB. |
| | |
| | 5) P101: PROVIDE GREASE WASTE CALCULATIONS AND AN |
| | EQUIPMENT SCHEDULE ON THE PLAN FOR THE GREASE |
| | INTERCEPTOR- SECTIONS 1003.3.4 & 1003.3.6 FBC P. PLEASE |
| | NOTE THAT ALL REVISIONS TO THE GREASE WASTE SYSTEM ON |
| | THE MASTER PERMIT SHALL ALSO BE APPLICABLE TO THE |
| | GREASE INTERCEPTOR PERMIT- 19060937. |
| | |
| | 6) P102, P201: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | TANKLESS WATER HEATERS INDICATING THE MAKES, MODEL |
| | NUMBERS, BTUH CAPACITIES, LISTING STANDARDS, AND |
| | EFFICIENCY RATINGS- SECTION 624.1 FBC FG, AND TABLE |
| | C404.2 FBC EC. A) PROVIDE A FRONT ELEVATION VIEW OF THE |
| | WATER HEATER MOUNTING LOCATION SHOWING CLEARANCE |
| | DISTANCES FROM GRADE, OVERHEAD CONSTRUCTION, AND |
| | MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE |
| | BUILDING- SECTION 624.1 AND 503.1 FBC FG. |
| | |
| | 7) P102 & P202: SHOW THE LOCATION OF THE HOT WATER |
| | CIRCULATION PUMP AND PROVIDE AN EQUIPMENT SCHEDULE- |
| | SECTION 607.2.1 FBC P. |
| | |
| | 8) P102, P201: INDICATE THE TYPE AND THICKNESS OF THE |
| | HOT WATER PIPING INSULATION TO BE INSTALLED ON THE |
| | EXTERIOR AND INTERIOR HOT WATER PIPING- TABLE C403.2.10 |
| | FBC EC. |
| | |
| | 9) P102 & P202: PROVIDE A PLUMBING DEVICE SCHEDULE |
| | INDICATING THE MAKES AND MODEL NUMBERS OF THE MIXING |
| | VALVES, BACKFLOW PREVENTERS, WATER HAMMER ARRESTORS, |
| | AND TRAP PRIMERS- SECTIONS 607.1.2, 608.1, 604.9, |
| | 1002.4.1.1 FBC P. PLEASE INCLUDE THE LISTING NUMBERS OF |
| | THE DEVICES. |
| | |
| | 10) P103: SHOW THE LOCATIONS OF TRAP PRIMERS ON THE |
| | RISER DRAWINGS- SECTION 1002.4.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |