| 2020-12-09 17:39:05 | 2ND REVIEW FBC-2017 RES. PLUMBING |
| | PERMIT- 20100209 |
| | 12/9/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS 10A & 10B: THE NEW WATER RISERS SHOW 3/8 IN. |
| | FIXTURE SUPPLY PIPES TO THE 1ST FLOOR SINKS, WASHING |
| | MACHINE, AND THE 2ND FLOOR BATHTUB, SHOWERS, AND SINKS. |
| | PLEASE REFER TO SECTIONS P2601.1 P2903.8.2 FBC RES, AND |
| | TABLE 604.5 FBC P AND PROVIDE MIN. 1/2 IN. SUPPLY PIPES |
| | TO THE FIXTURES. |
| | |
| | 2) SHEETS 10,10A, & 10B: BASED ON THE NEW NOTES |
| | CONCERNING THE HOT WATER SYSTEM IT APPEARS A |
| | RECIRCULATING PUMP WILL BE INSTALLED. ARE THE TANKLESS |
| | WATER HEATERS EQUIPPED WITH RECIRCULATION PUMPS OR WILL |
| | A SEPARATE PUMP BE INSTALLED? PLEASE PROVIDE ADDITIONAL |
| | INFORMATION AND DETAILS- SECTION 107.2.1 WPB. PLEASE |
| | REVISE THE NOTES TO INDICATE THE APPLICABLE CODE |
| | SECTIONS FROM THE FBC RES AND FBC EC. |
| | |
| | 3) COMMENT #5 FROM THE 1ST REVIEW CONCERNING THE HOT |
| | WATER SYSTEM PARTIALLY ADDRESSED. PLEASE PROVIDE WATER |
| | HEATER EQUIPMENT SCHEDULES THAT INCLUDE THE EFFICIENCY |
| | RATINGS ON THE PLAN AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS- SECTIONS P2801.3 & G2448.1 FBC RES. |
| | |
| | 4) SHEET 10: 2ND REQUEST TO SHOW A TWO-WAY CLEANOUT |
| | WILL BE INSTALLED AT THE BUILDING DRAIN/SEWER PIPE |
| | JUNCTIONS- SECTION P3005.2.8 FBC RES. |
| | |
| | 5) SHEET 10: AS PREVIOUSLY NOTED A SEPARATE PERMIT AND |
| | PLANS ARE REQUIRED FOR THE GAS PIPING INSTALLATIONS- |
| | SECTIONS 105.1 & 107.2.1 WPB. A COMPLETE REVIEW OF THE |
| | REQUIRED GAS PIPING SYSTEMS, THE APPLIANCES AND |
| | GENERATOR SHOWN ON THE PLAN, AND THE REQUIRED |
| | COMBUSTION AIR AND VENTING PLANS WILL NOT BE PERFORMED |
| | UNDER THIS PERMIT. |
| | |
| | 6) 2ND REQUEST FOR A PLUMBING SUB-PERMIT- SECTION 105.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |