| 2020-12-15 09:29:43 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | |
| | ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW. |
| | |
| | FROM PREVIOUS COMMENTS: |
| | |
| | 1. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTOR SIZES WHEN |
| | MORE THAN ONE PANEL SERVES A DWELLING. NEC 310.15 (B) |
| | (7) (1) NEC 230.23(A). SIZE 3/0 IS REQUIRED FOR 200AMP |
| | SERVICE ENTRANCE CONDUCTORS AND 1/0 IS REQUIRED FOR |
| | 150AMP SERVICE ENTRANCE CONDUCTORS |
| | |
| | THE 150 AMPS SERVICE WAS CHANGED TO 200 AMPS AND IT |
| | WILL ALSO REQUIRE A SIZE 3/0 SERVICE ENTRANCE |
| | CONDUCTOR. PLEASE CORRECT. |
| | |
| | NEW COMMENTS: |
| | |
| | 2. A NEW STEAM UNIT WAS ADDED TO PLANS. THE STEAM UNIT |
| | SPECS INDICATES A 7.2 KW/31AMPS LOAD WITH A 40 AMPS |
| | FUSE, BUT PANEL SCHEDULE SHOWS A 12KW LOAD WITH 50 AMPS |
| | BREAKER. PLEASE CORRECT DISCREPANCIES. |
| | |
| | 3. PLEASE SHOW CIRCUIT AND DISCONNECT FOR STEAM UNIT ON |
| | POWER PLAN |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |