| 2020-12-11 18:00:03 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | ******NOTE: |
| | SINCE THERE ARE TWO SEPARATE BUILDINGS IN THIS |
| | PROPERTY, THEN A SEPARATE PERMIT APPLICATION WILL BE |
| | REQUIRED FOR EACH EACH BUILDING. ONE FOR THE MAIN HOUSE |
| | AND ONE FOR THE GUEST CASITA. |
| | I GENERATED A NEW PERMIT NUMBER 20120600 FOR THE GUEST |
| | CASITA USING THE SAME APPLICATION SUBMITTED FOR THE |
| | MAIN HOUSE. GUEST CASITA APPLICATION WAS UPLOADED T |
| | PROJECTDOX. SAME PLANS CAN BE USED. I WILL CONTACT |
| | CONTRACTOR TO CLARIFY/COORDINATE. |
| | SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE |
| | INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS |
| | KEEPING. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO IF SURVEY |
| | OR SITE PLAN IS PROVIDED SHOWING THE BUILDINGS |
| | SETBACKS. |
| | |
| | PROVISO MEANS CONTRACTOR WILL SUBMIT REQUIRED |
| | INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE |
| | INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES |
| | MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS |
| | PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | R101.5.1 FBC-ENERGY CONSERVATION. |
| | NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL |
| | REQUIRED PARTIES, INCLUDING THE OWNER OR LEGALLY |
| | AUTHORIZED AGENT. |
| | |
| | RESPONSE: |
| | ENERGY CALCULATIONS SUBMITTED: |
| | A)THERE ARE TWO SEPARATE BUILDINGS IN THIS PROPERTY. |
| | MAIN HOUSE AND GUEST CASITA. NEED A SEPARATE ENERGY |
| | CALCULATIONS FOR EACH BUILDING. |
| | SEC. R101.2 FBC-ENERGY CONSERVATION. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER, BUILDER AND PERMIT OFFICE AND |
| | JURISDICTION NUMBER (THIS JURISDICTION IS 604700) . |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | C)REVISE A/C AREA. MAIN HOUSE AND GUEST CASITA AREA TO |
| | BE DONE ON SEPARATE FORMS FOR EACH BUILDING. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | D)REVISE WALL TYPE IN ITEM #9 ON PAGE 1 OF 6. ACCORDING |
| | TO PLANS THESE ARE WOOD BEARING WALLS. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | E)PAGE 2 OF 6 SHOWS A KITCHEN IN-THE GUEST CASITA. |
| | THERE IS NOT KITCHEN IN THE GUEST CASITA. REVISE THIS |
| | WHEN DOING GUEST CASITA ON SEPARATE FORM. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | F)REVISE/CLARIFY DOORS INFORMATION ON PAGE 4 OF 6. |
| | WHERE IS THE 6 X 8 WOOD DOOR BY THE KITCHEN ZONE. SEE |
| | PLANS AND PRODUCT APPROVALS AND REVISE AS REQUIRED. |
| | ALSO, WHERE ARE THE OTHER TWO WOOD DOORS?. NOTE: |
| | GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE WINDOW |
| | GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY |
| | CONSERVATION). |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | G)PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS |
| | AND GENERATING THE REPORT AS REQUIRED BY SEC. |
| | R405.4.2.1 FBC- ENERGY CONSERVATION. |
| | |
| | H)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS. |
| | SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| | |
| | ORIGINAL COMMENT: |
| | 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| | FOLLOWING: |
| | R401.3 FBC-RESIDENTIAL. |
| | SEC. 107.2.5 CITY AMENDMENTS. |
| | SEC. 110.9 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. PROVIDE COMPLETE SITE |
| | PLAN DRAWN TO SCALE SHOWING THE BUILDINGS AND PROPOSED |
| | DRAINAGE. ALSO, SHOW THE DISTANCES FROM LOT LINES, ETC. |
| | SEE SEC. 107.2.5 CITY AMENDMENTS. |
| | |
| | 3- OK |
| | 4- OK |
| | 5-OK |
| | |
| | 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO |
| | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT |
| | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL): |
| | |
| | RESPONSE: |
| | PRODUCT APPROVALS NEED TO BE COORDINATED. PRODUCT |
| | APPROVALS UPLOADED TO PROJECTDOX AND PRODUCT APPROVALS |
| | LISTED ON THE SEPARATE ENGINEER'S LETTER (PRODUCT |
| | APPROVAL) AND PRODUCT APPROVALS LISTED ON THE PRODUCT |
| | APPROVAL SCHEDULE ON SHEET 3 OF 10 DON'T MATCH. |
| | PLEASE COORDINATE ALL PRODUCT APPROVALS, PRODUCT |
| | APPROVALS NUMBERS, ETC AND RESUBMIT. NOTE: TO AVOID |
| | CONFLICTS/DELAYS THIS CAN BE DONE LATER AFTER THE |
| | PERMIT IS ISSUED. NO PLAN REVIEW FEE FOR THIS. ALSO, |
| | SEE COMMENT BELOW FOR GARAGE DOOR. |
| | |
| | ******GARAGE DOOR NOA 20-0107.06 SUBMITTED. DOESN'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF |
| | RECROD AND NOA DOESN'TMATCH ONE SPECIFIED ON THE |
| | PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10. |
| | |
| | ***DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | |
| | 7-HOUSE IS DESIGNED WITH UNVENTED ATTIC. DESIGNER OF |
| | RECORD IS SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE |
| | ICC EVALUATION REPORT FOR THE ICYNENE INSULATION TO |
| | VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. |
| | NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE |
| | REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | RESPONSE: |
| | NO SUBMITTED. NOTE: THIS MAY BE SUBMITTED LATER AS A |
| | DEFERRED SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR |
| | TO INSTALLATION TO AVOID CONFLICTS/DELAYS. |
| | |
| | 8-PROVISO: HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL: |
| | PROVIDE SHOP DRAWINGS REVIEWED BY THE DESIGN |
| | PROFESSIONAL OF RECORD PRIOR TO INSTALLATION TO AVOID |
| | CONFLICTS/DELAYS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |