Plan Review Notes
Plan Review Notes For Permit 20100209
Permit Number 20100209
Review Stop B
Sequence Number 2
Notes
Date Text
2020-12-11 18:00:03RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ******NOTE:
 SINCE THERE ARE TWO SEPARATE BUILDINGS IN THIS
 PROPERTY, THEN A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR EACH EACH BUILDING. ONE FOR THE MAIN HOUSE
 AND ONE FOR THE GUEST CASITA.
 I GENERATED A NEW PERMIT NUMBER 20120600 FOR THE GUEST
 CASITA USING THE SAME APPLICATION SUBMITTED FOR THE
 MAIN HOUSE. GUEST CASITA APPLICATION WAS UPLOADED T
 PROJECTDOX. SAME PLANS CAN BE USED. I WILL CONTACT
 CONTRACTOR TO CLARIFY/COORDINATE.
 SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 KEEPING. SEC. 107.2.1.3 CITY AMENDMENTS.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO IF SURVEY
 OR SITE PLAN IS PROVIDED SHOWING THE BUILDINGS
 SETBACKS.
  
 PROVISO MEANS CONTRACTOR WILL SUBMIT REQUIRED
 INFORMATION AFTER THE PERMIT IS ISSUED BUT BEFORE
 INSPECTIONS TO AVOID CONFLICTS/DELAYS. REVISION FEES
 MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORMS ARE PROPERLY SIGNED BY ALL
 REQUIRED PARTIES, INCLUDING THE OWNER OR LEGALLY
 AUTHORIZED AGENT.
  
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A)THERE ARE TWO SEPARATE BUILDINGS IN THIS PROPERTY.
 MAIN HOUSE AND GUEST CASITA. NEED A SEPARATE ENERGY
 CALCULATIONS FOR EACH BUILDING.
 SEC. R101.2 FBC-ENERGY CONSERVATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER AND PERMIT OFFICE AND
 JURISDICTION NUMBER (THIS JURISDICTION IS 604700) .
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)REVISE A/C AREA. MAIN HOUSE AND GUEST CASITA AREA TO
 BE DONE ON SEPARATE FORMS FOR EACH BUILDING.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)REVISE WALL TYPE IN ITEM #9 ON PAGE 1 OF 6. ACCORDING
 TO PLANS THESE ARE WOOD BEARING WALLS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)PAGE 2 OF 6 SHOWS A KITCHEN IN-THE GUEST CASITA.
 THERE IS NOT KITCHEN IN THE GUEST CASITA. REVISE THIS
 WHEN DOING GUEST CASITA ON SEPARATE FORM.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)REVISE/CLARIFY DOORS INFORMATION ON PAGE 4 OF 6.
 WHERE IS THE 6 X 8 WOOD DOOR BY THE KITCHEN ZONE. SEE
 PLANS AND PRODUCT APPROVALS AND REVISE AS REQUIRED.
 ALSO, WHERE ARE THE OTHER TWO WOOD DOORS?. NOTE:
 GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE WINDOW
 GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 H)REVISE WINDOWS OVERHANG SEPARATION TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. PROVIDE COMPLETE SITE
 PLAN DRAWN TO SCALE SHOWING THE BUILDINGS AND PROPOSED
 DRAINAGE. ALSO, SHOW THE DISTANCES FROM LOT LINES, ETC.
 SEE SEC. 107.2.5 CITY AMENDMENTS.
  
 3- OK
 4- OK
 5-OK
  
 6-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 RESPONSE:
 PRODUCT APPROVALS NEED TO BE COORDINATED. PRODUCT
 APPROVALS UPLOADED TO PROJECTDOX AND PRODUCT APPROVALS
 LISTED ON THE SEPARATE ENGINEER'S LETTER (PRODUCT
 APPROVAL) AND PRODUCT APPROVALS LISTED ON THE PRODUCT
 APPROVAL SCHEDULE ON SHEET 3 OF 10 DON'T MATCH.
 PLEASE COORDINATE ALL PRODUCT APPROVALS, PRODUCT
 APPROVALS NUMBERS, ETC AND RESUBMIT. NOTE: TO AVOID
 CONFLICTS/DELAYS THIS CAN BE DONE LATER AFTER THE
 PERMIT IS ISSUED. NO PLAN REVIEW FEE FOR THIS. ALSO,
 SEE COMMENT BELOW FOR GARAGE DOOR.
  
 ******GARAGE DOOR NOA 20-0107.06 SUBMITTED. DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF
 RECROD AND NOA DOESN'TMATCH ONE SPECIFIED ON THE
 PRODUCT APPROVAL SCHEDULE ON SHEET 3 OF 10.
  
 ***DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 7-HOUSE IS DESIGNED WITH UNVENTED ATTIC. DESIGNER OF
 RECORD IS SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE INSULATION TO
 VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: DESIGNER OF RECORD TO REVIEW AND APPROVE THE
 REPORT IN WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 NO SUBMITTED. NOTE: THIS MAY BE SUBMITTED LATER AS A
 DEFERRED SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR
 TO INSTALLATION TO AVOID CONFLICTS/DELAYS.
  
 8-PROVISO: HANDRAILS AND GUARDRAILS DEFERRED SUBMITTAL:
 PROVIDE SHOP DRAWINGS REVIEWED BY THE DESIGN
 PROFESSIONAL OF RECORD PRIOR TO INSTALLATION TO AVOID
 CONFLICTS/DELAYS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  