| Plan Review Notes For Permit 20100209 |
| Permit Number |
20100209 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-27 09:43:13 | 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR: | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO | | | INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT | | | APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL): | | | | | | A) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | B) ROOF TILE AND CLEARLY SPECIFY ROOF TILE FASTENING | | | METHOD AS REQUIRED BY CITY POLICY FOR ALL ROOFING | | | PERMITS. FOR MECHANICALLY ATTACHED TILE PROVIDE | | | COMPLETE TILE FASTENING INFORMATION. | | | | | | C)ROOF TILE ADHESIVE IF SELECTED AS THE FASTENING | | | METHOD. CLEARLY IDENTIFY PADDY SIZE. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|