Plan Review Notes
Plan Review Notes For Permit 20100209
Permit Number 20100209
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-22 12:43:071ST REVIEW FBC-2017 RES. PLUMBING
 PERMIT- 20100209
 10/22/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 2) PLEASE NOTE A SEPARATE PERMIT AND PLANS ARE REQUIRED
 FOR THE GAS PIPING INSTALLATIONS- SECTIONS 105.1 &
 107.2.1 WPB. A COMPLETE REVIEW OF THE REQUIRED GAS
 PIPING SYSTEMS, THE APPLIANCES AND GENERATOR SHOWN ON
 THE PLAN, AND THE REQUIRED COMBUSTION AIR AND VENTING
 PLANS WILL NOT BE PERFORMED UNDER THIS PERMIT.
  
 3) PLEASE PROVIDE A PLUMBING FLOOR PLAN AND SITE
 DRAWING SHOWING THE SANITARY DRAINAGE AND WATER
 DISTRIBUTION PIPING LAYOUTS INCLUDING THE LOCATIONS OF
 THE WATER METER, MAIN SHUTOFFS VALVES FOR THE MAIN
 HOUSE AND GUEST HOUSE, LOCATIONS OF BACKFLOW PREVENTERS
 FOR THE MAIN POTABLE WATER SUPPLY SYSTEMS, AND AT WATER
 SUPPLY CONNECTIONS TO IRRIGATION SYSTEMS AND POOL
 EQUIPMENT, AND LOCATIONS OF HOSE BIBS- SECTION 107.2.1
 WPB AND SECTIONS P2902.1, P2902.1, P2903.1 & P2903.9
 FBC RES. PLEASE PROVIDE COMPLETE PLUMBING NOTES
 INDICATING AT A MINIMUM THE TYPES OF PIPING MATERIALS,
 FIXTURE SHUTOFF VALVES, INDIVIDUAL BATHTUB AND SHOWER
 VALVES, AND PIPE INSULATIONS TO BE INSTALLED ETC.-
 P2609 FBC RES.
  
 4) SHEET 10 SANITARY RISER:
  
 A) SHOW THE REQUIRED 3 IN. FIXTURE BRANCH DRAINS AND
 STACKS FOR THE WASHING MACHINES- SECTION 406.2 FBC P.
  
 B) SHOW THE REQUIRED CLEANOUTS AT THE BASES OF THE 3
 VERTICAL STACKS- SECTION P3005.2.4 FBC RES.
  
 C) THE WATER CLOSET IN THE ENSUITE BATHROOM WILL
 REQUIRE AN INDIVIDUAL VENT BECAUSE IT IS NOT PART OF
 THE BATHROOM WET VENT- NOT MORE THAN ONE WET-VENTED
 FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF THE
 DRY-VENTED FIXTURE DRAIN CONNECTION- SECTION P3108.2.1
 FBC RES.
  
 D) SHOW THE DISHWASHER DRAIN CONNECTION- SECTION
 P2717.2 FBC RES.
  
 E) PROVIDE A CLEANOUT AT THE JUNCTION OF THE GUEST
 HOUSE BUILDING DRAIN AND BUILDING SEWER- SECTION
 P3005.2.3 FBC RES. SHOW A TWO-WAY CLEANOUT WILL BE
 INSTALLED BUILDING DRAIN/SEWER PIPE JUNCTIONS- SECTION
 P3005.2.8 FBC RES.
  
 F) SHOW THE LOCATION OF THE CLEANOUT FOR THE OUTDOOR
 PATIO SINK- SECTION P3003.5.2.
  
 G) IT APPEARS THAT THE DRAIN AND VENT FOR ONE OF THE
 KITCHEN ISLAND SINKS IS MISSING FROM THE DRAWING-
 SECTION 107.2.1 WPB.
  
 5) INDICATE HOW HOT WATER WILL BE PROVIDED TO THE
 FIXTURES- SECTION P2801.1 FBC RES. PROVIDE A FLOOR PLAN
 DRAWING SHOWING THE LOCATIONS OF THE WATER HEATERS.
 PROVIDE EQUIPMENT SCHEDULES ON THE PLAN AND SUBMIT
 MANUFACTURER?S SPECIFICATIONS- SECTIONS P2801.3 &
 G2448.1 FBC RES. IT APPEARS FROM THE ELECTRICAL
 DRAWINGS THAN GAS-FIRED TANKLESS WATER HEATERS WILL BE
 INSTALLED. PLEASE PROVIDE PIPING DIAGRAMS FOR THE
 UNITS.
  
 6) PROVIDE A WATER RISER DRAWING PER SECTION 107.2.3.2
 WPB. SHOW PIPE SIZES AND LOCATIONS OF SHUTOFF VALVES,
 BACKFLOW PREVENTERS, WATER HAMMER ARRESTORS ETC. PLEASE
 NOTE THAT WATER HAMMERS ARE REQUIRED FOR SUPPLY LINES
 TO THE WASHING MACHINES, DISHWASHERS AND ICE MAKERS-
 SECTION P2903.5 FBC RES. BACKFLOW PREVENTERS ARE
 REQUIRED FOR SUPPLY LINES TO THE STEAM UNIT AND ICE
 MAKERS- SECTION P2902.3. THE SUPPLY LINE DISHWASHER
 SHALL BE PROTECTED AGAINST BACKFLOW BY AN AIR GAP OR
 BACKFLOW PREVENTER- SECTION P2717.1.
  
 7) INDICATE HOW WATER UNDERGROUND PIPING AND PIPING
 PENETRATING CONCRETE SLABS WILL BE PROTECTED AGAIN
 CORROSION- SECTION P2603.3.
  
 8) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 STEAM UNIT AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION MANUAL - SECTION M1307.1 FBC RES.
  
 9) INDICATE HOW CONDENSATE FROM THE STEAM UNIT AND ICE
 MAKER WILL BE DRAINED AND DISPOSED. SHOW THE TYPE AND
 SIZE OF PIPING, PIPING RUNS, AND DISCHARGE LOCATIONS-
 SECTION 314 FBC P.
  
 10) PROVIDE ENLARGED SHOWER RECESS AND SHOWER PAN
 DETAILS- SECTIONS P2709.1 & P2709.2 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  