| 2021-01-06 17:52:39 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100209 |
| | 10/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. A COMPLETE REVIEW OF THE |
| | GAS PLANS WAS NOT COMPLETED AT THIS TIME DUE A LACK OF |
| | INFORMATION PROVIDED ON THE PLANS. PLEASE REVIEW THE |
| | COMMENTS BELOW AND RESUBMIT COMPLIANT PLANS AND |
| | SPECIFICATIONS. |
| | |
| | 1) SHEET 10 GAS RISER CORRECTIONS- FBC-17 RES. FUEL |
| | GAS: |
| | A) PROVIDE THE DELIVERY PRESSURE AT THE METER- G2413.1. |
| | B) CORRECT THE TOTAL BTU LOAD TO 1020 K- SECTION |
| | G2413.2. |
| | C) PROVIDE THE TYPES AND SIZES OF BRANCH PIPING TO THE |
| | TANKLESS WATER HEATERS AND THE RANGE- G2413.4.1 & |
| | G2413.4.2. |
| | D) LIST THE PIPE SIZING TABLES USED TO DESIGN THE |
| | SYSTEM- G2413.3 & G2413.4. |
| | |
| | 2) LIST THE MAKES AND MODELS OF THE WATER HEATERS AND |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS- G2448.1. THE |
| | SPECS AND INSTALL MANUALS MAY BE DEFERRED AND SUBMITTED |
| | AT A LATER DATE, BUT ALL SPECS AND INSTALL MANUALS |
| | SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS 107.2.1 |
| | AND 107.3.4.1 WPB. |
| | |
| | 3) LIST THE MAKES AND MODELS OF THE FIREPLACE, FIREPIT, |
| | POOL HEATER, DRYER, RANGE, AND BBQ GRILL ON THE PLAN |
| | AND SUBMIT MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE |
| | THE SPECS AND INSTALL MANUALS MAY BE DEFERRED AND |
| | SUBMITTED AT A LATER DATE, BUT ALL SPECS AND INSTALL |
| | MANUALS SHALL BE ONSITE AT TIME OF INSPECTION- SECTIONS |
| | 107.2.1 AND 107.3.4.1 WPB. |
| | |
| | 4) SUBMIT MARKED UP OR HIGHLIGHTED REGULATOR SPECS |
| | SHOWING THE SELECTED MODELS, THE MAX INLET AND OUTLET |
| | SIZES AND PRESSURES AND ORIFICE SIZES. THE SPECS MAY BE |
| | DEFERRED AND BE ONSITE FOR INSPECTION. |
| | |
| | 5) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE GAS |
| | RANGE AND THE FIREPLACE AND SHOW HOW THE AIR IS BEING |
| | PROVIDED- SECTION G2407.1. |
| | |
| | 6) PROVIDE MAKEUP AIR CALCULATIONS FOR THE DRYER AND |
| | SHOW HOW THE AIR IS BEING PROVIDED- G2439.5. |
| | |
| | 7) PROVIDE A VENTING DIAGRAM FOR THE FIREPLACE SHOWING |
| | THE TYPE AND SIZE OF VENT FLUE, VENT RUN, AND |
| | TERMINATION LOCATION- G2427.8(3). |
| | |
| | 8) PLEASE SHOW THE LOCATION OF THE FIREPIT ON THE FLOOR |
| | PLAN DRAWINGS- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |