Plan Review Notes
Plan Review Notes For Permit 20100209
Permit Number 20100209
Review Stop E
Sequence Number 1
Notes
Date Text
2020-10-26 22:24:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTOR SIZES WHEN
 MORE THAN ONE PANEL SERVES A DWELLING. NEC 310.15 (B)
 (7) (1) NEC 230.23(A)
  
 3/0 IS REQUIRED FOR 200AMP SERVICE ENTRANCE CONDUCTORS
 AND 1/0 IS REQUIRED FOR 150AMP SERVICE ENTRANCE
 CONDUCTORS
  
 2. "OPTIONAL" GENERATOR MUST BE REMOVED FROM PLANS. IF
 AND WHEN A GENERATOR IS INSTALLED IT IS REQUIRED TO BE
 INSTALLED WITH A SEPARATE STAND ALONE PERMIT. FBC 105.1
 FBC 107.2.1
  
 3. ELECTRICAL NOTE #8 DOES NOT LIST LAUNDRY ROOMS FOR
 AFCI PROTECTION. PROVIDE CORRECTION. NEC210.12A
  
 4. ALARMS OUTSIDE OF BEDROOMS MUST BE SMOKE/CARBON
 ALARMS WHEN THE HOME HAS A GAS APPLIANCE, FIREPLACE, OR
 ATTACHED GARAGE PER FBC RE 314 &315 PROVIDE CORRECTION.
  
 5. PROVIDE NOTE ON PLAN ALL LOW VOLTAGE SYSTEMS WILL
 REQUIRE A SEPARATE PERMIT. FBC 107.2.1
  
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  