| 2020-10-26 22:24:54 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. CANNOT DE-RATE SERVICE ENTRANCE CONDUCTOR SIZES WHEN |
| | MORE THAN ONE PANEL SERVES A DWELLING. NEC 310.15 (B) |
| | (7) (1) NEC 230.23(A) |
| | |
| | 3/0 IS REQUIRED FOR 200AMP SERVICE ENTRANCE CONDUCTORS |
| | AND 1/0 IS REQUIRED FOR 150AMP SERVICE ENTRANCE |
| | CONDUCTORS |
| | |
| | 2. "OPTIONAL" GENERATOR MUST BE REMOVED FROM PLANS. IF |
| | AND WHEN A GENERATOR IS INSTALLED IT IS REQUIRED TO BE |
| | INSTALLED WITH A SEPARATE STAND ALONE PERMIT. FBC 105.1 |
| | FBC 107.2.1 |
| | |
| | 3. ELECTRICAL NOTE #8 DOES NOT LIST LAUNDRY ROOMS FOR |
| | AFCI PROTECTION. PROVIDE CORRECTION. NEC210.12A |
| | |
| | 4. ALARMS OUTSIDE OF BEDROOMS MUST BE SMOKE/CARBON |
| | ALARMS WHEN THE HOME HAS A GAS APPLIANCE, FIREPLACE, OR |
| | ATTACHED GARAGE PER FBC RE 314 &315 PROVIDE CORRECTION. |
| | |
| | 5. PROVIDE NOTE ON PLAN ALL LOW VOLTAGE SYSTEMS WILL |
| | REQUIRE A SEPARATE PERMIT. FBC 107.2.1 |
| | |
| | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | |
| | |
| | |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |