| 2020-10-13 14:12:34 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT- 20100153 |
| | 10/13/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) PROVIDE A MARKED-UP SURVEY DRAWING TO SHOW THE |
| | LOCATION OF THE UNDERGROUND PE LINE RUN- SECTION |
| | 107.2.1 WPB. VERIFY THE LOCATION IS NOT OUTSIDE THE |
| | PROPERTY LINES, IN A RIGHT OF WAY, OR IN A UTILITY |
| | EASEMENT. |
| | |
| | 2) SHOW THE LOCATION, OR LOCATIONS OF THE NEW OR |
| | EXISTING LOW PRESSURE REGULATORS FOR THE EXISTING |
| | APPLIANCES AND EQUIPMENT- SECTION 410.1 & 401.2 FBC FG. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECS FOR THE REGULATORS |
| | MARKED UP TO SHOW THE SELECTED MODEL, INLET AND OUT |
| | PRESSURES AND PIPE SIZES- SECTION 410.2. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |