| 2020-11-16 09:32:10 | PLAN REVIEW / BUILDING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER BUILDING - PX3169 |
| | PLANS EXAMINER 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NEC 2014 |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | |
| | 1. PROVIDE PROJECT DATA / DESIGN PARAMETERS: (AS |
| | APPLICABLE) |
| | |
| | PROJECT DATA: 1&2 FAMILY DWELLING UNIT |
| | |
| | SITE PLAN/SURVEY |
| | DRAINAGE PLAN: (IF APPLICABLE) |
| | SCOPE OF WORK: |
| | PROPERTY INFO: |
| | PCN #: |
| | FLOOD ZONE: (IF APPLICABLE) |
| | FINISHED FLOOR ELEVATION: (IF APPLICABLE) |
| | |
| | GOVERNING CODES: (AS APPLICABLE) |
| | |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FBC RESIDENTIAL BUILDING CODE - |
| | MECHANICAL/ELECTRICAL/PLUMBING/FUEL GAS |
| | 2017 FBC EXISTING BUILDING CODE |
| | 2014 NEC |
| | |
| | DESIGN PARAMETERS: |
| | |
| | SITE SPECIFIC DESIGN WIND LOADS PER ASCE 7-10 |
| | (VULT 170MPH 3 SEC GUST / VASD 132MPH) |
| | EXPOSURE CLASSIFICATION - C |
| | RISK CATEGORY - 2 |
| | STRUCTURE - ENCLOSED / OPEN |
| | MRH - |
| | |
| | BUILDING CLASSIFICATION - VB |
| | OCCUPANCY CLASSIFICATION - R3 SFR |
| | |
| | CLASSIFICATION OF WORK: ALTERATION LEVEL III |
| | |
| | |
| | 2. PROVIDE DESIGN PRESSURES FOR WINOWS/DOORS/ROOFS: |
| | |
| | WINDOWS AND DOORS - ZONE 4 INT. / ZONE 5 CORNER |
| | (POSITVE/NEGATIVE) |
| | ROOF - ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS) |
| | - (NEGATIVE PRESSURE ONLY) |
| | |
| | FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN |
| | PRESSURES PURSUANT TO FBC-R301.2. |
| | |
| | R301.2.1 WIND DESIGN CRITERIA. |
| | BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING |
| | THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED |
| | FROM FIGURE R301.2(4). |
| | |
| | 3. ADD DOWELS FROM EXISTING FOOTING TO NEW FOOTING AT |
| | BATH #1 BUILD-OUT. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 4. PROVIDE AN ENERGY SUBMITTAL. |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC |
| | EC. |
| | |
| | PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM |
| | SIZING CALCULATIONS- SECTION R403.7.1 FBC EC. |
| | |
| | 5. ROOFING PERMIT IS REQUIRED. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 6. PROVIDE PRODUCT APPROVALS FOR NEW EXT. DOORS AND |
| | WINDOWS. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |