Plan Review Notes
Plan Review Notes For Permit 20100110
Permit Number 20100110
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-16 09:32:10PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PROVIDE PROJECT DATA / DESIGN PARAMETERS: (AS
 APPLICABLE)
  
 PROJECT DATA: 1&2 FAMILY DWELLING UNIT
  
 SITE PLAN/SURVEY
 DRAINAGE PLAN: (IF APPLICABLE)
 SCOPE OF WORK:
 PROPERTY INFO:
 PCN #:
 FLOOD ZONE: (IF APPLICABLE)
 FINISHED FLOOR ELEVATION: (IF APPLICABLE)
  
 GOVERNING CODES: (AS APPLICABLE)
  
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FBC RESIDENTIAL BUILDING CODE -
 MECHANICAL/ELECTRICAL/PLUMBING/FUEL GAS
 2017 FBC EXISTING BUILDING CODE
 2014 NEC
  
 DESIGN PARAMETERS:
  
 SITE SPECIFIC DESIGN WIND LOADS PER ASCE 7-10
 (VULT 170MPH 3 SEC GUST / VASD 132MPH)
 EXPOSURE CLASSIFICATION - C
 RISK CATEGORY - 2
 STRUCTURE - ENCLOSED / OPEN
 MRH -
  
 BUILDING CLASSIFICATION - VB
 OCCUPANCY CLASSIFICATION - R3 SFR
  
 CLASSIFICATION OF WORK: ALTERATION LEVEL III
  
  
 2. PROVIDE DESIGN PRESSURES FOR WINOWS/DOORS/ROOFS:
  
 WINDOWS AND DOORS - ZONE 4 INT. / ZONE 5 CORNER
 (POSITVE/NEGATIVE)
 ROOF - ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS)
 - (NEGATIVE PRESSURE ONLY)
  
 FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
  
 3. ADD DOWELS FROM EXISTING FOOTING TO NEW FOOTING AT
 BATH #1 BUILD-OUT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 PROVIDE ENERGY GAUGE FORM R405 PER SECTION R405.2 FBC
 EC.
  
 PROVIDE THE MANUAL J WORKSHEETS WITH THE AC SYSTEM
 SIZING CALCULATIONS- SECTION R403.7.1 FBC EC.
  
 5. ROOFING PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 6. PROVIDE PRODUCT APPROVALS FOR NEW EXT. DOORS AND
 WINDOWS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  
  
  
  