| Plan Review Notes For Permit 20100104 |
| Permit Number |
20100104 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2021-02-11 12:57:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-1 LOAD CALCULATION FOR FEEDER TO PANEL EV NOT IN | | | ACCORDANCE WITH 625.40. | | | | | | PAGE E-2 LOAD CALCULATION FOR FEEDER TO EAST LOT PANEL | | | NOT IN ACCORDANCE WITH 625.40. | | | | | | PAGE AREA 1 SHOWS A FEEDER WITH 3 #1 AND A #6 AND | | | ANOTHER BRANCH GOING TO THE HANDICAP SPACE WHAT FEEDS | | | THE HANDICAP SPACE. WHERE IS THE HANDICAP FED FROM? | | | 125A MAIN/ 200A MAIN? | | | | | | PAGE AREA 2 SHOWS 3/0 GOING TO THE PANEL, LOAD | | | CALCULATION SHOWN FOR THESE CONDUCTORS IS NOT PER | | | 625.40. 200A MAIN/300A MAIN? | | | | | | PLEASE PROVIDE A VOLTAGE DROP CALCULATION BASED ON | | | 625.40 LOAD CALCULATION. | | | | | | DO YOU HAVE LOAD MANAGEMENT IF SO PLEASE EXPLAN HOW IT | | | WORKS. | | | | | | |
|