| Date |
Text |
| 2020-10-06 11:58:05 | 010/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR |
| | THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP |
| | FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN |
| | DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE TDH |
| | CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. |
| | |
| | 2. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| | IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| | TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS. |
| | 4.4.9, 4.4.9.1. |
| | |
| | 3. IT INDICATES ON THE PLANS THAT THERE IS NO POOL FILL |
| | AND ON THE CONTRACT, ON PAGE 4 IT CALLS OUT FOR FILL, |
| | PLEASE CLARIFY IF THE POOL IS EQUIPPED WITH AN |
| | AUTO-FILL PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. SINCE THIS A DUAL DWELLING AND IT HAS A BACKFLOW |
| | REDUCED PRESSURE ZONE BACKFLOW DEVICE IS REQUIRED PER |
| | THE CITY OF WEST PALM CROSS CONNECTION CONTROL MANUAL. |
| | |
| | 5. PLEASE PROVIDE FOR POOL HEATER SPECIFICATION THAT |
| | THE POOL HEATER HAS A MINIMUM THERMAL EFFICIENCY OF 82% |
| | PER THE 2017 FBC-ENERGY SEC. R403.10.4. |
| | |
| | 6. PLEASE PROVIDE ALL SPECIFICATIONS ON THE POOL FILTER |
| | AS IT DOES NOT SAY WHO THE MANUFACTURE IS OR MODEL TO |
| | INDENTIFY FLOW RATES PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |