Plan Review Notes
Plan Review Notes For Permit 20100086
Permit Number 20100086
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-06 11:58:05010/06/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR
 THE MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP
 FROM ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING THE MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2013 SECS.
 4.4.9, 4.4.9.1.
  
 3. IT INDICATES ON THE PLANS THAT THERE IS NO POOL FILL
 AND ON THE CONTRACT, ON PAGE 4 IT CALLS OUT FOR FILL,
 PLEASE CLARIFY IF THE POOL IS EQUIPPED WITH AN
 AUTO-FILL PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. SINCE THIS A DUAL DWELLING AND IT HAS A BACKFLOW
 REDUCED PRESSURE ZONE BACKFLOW DEVICE IS REQUIRED PER
 THE CITY OF WEST PALM CROSS CONNECTION CONTROL MANUAL.
  
 5. PLEASE PROVIDE FOR POOL HEATER SPECIFICATION THAT
 THE POOL HEATER HAS A MINIMUM THERMAL EFFICIENCY OF 82%
 PER THE 2017 FBC-ENERGY SEC. R403.10.4.
  
 6. PLEASE PROVIDE ALL SPECIFICATIONS ON THE POOL FILTER
 AS IT DOES NOT SAY WHO THE MANUFACTURE IS OR MODEL TO
 INDENTIFY FLOW RATES PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved