| Date |
Text |
| 2020-12-07 10:23:05 | 2ND REQUEST.ROOFING. RESPONSE INDICATES TO VIEW SHEET |
| | A2.2. FOR INFORMATION REQUIRED. THE BUILDING DEPARTMENT |
| | REQUIRES ALL THE IMPORTANT INFORMATION TO BE FILED OUT |
| | WITHIN THE PRODUCT APPROVAL (LISTED BELOW FOR EACH |
| | ROOFING PRODUCT APPROVAL, SYSTEM AND SUB-SYSTEM BY |
| | EITHER THE CONTRACTOR AND BEING REVIEWED BY THE |
| | DESIGNER OF RECORD AND APPLYING THEIR SHOP DRAWING OF |
| | APPROVAL, OR IN THE CASE WHERE NO CONTRACTOR HAS BEEN |
| | CHOSEN AND THE DESIGNER OF RECORD IS PICKING OUT THE |
| | PRODUCT APPROVALS, THEN THEY ARE THE ONES CHOOSING THE |
| | SYSTEMS, SUB-SYSTEMS AND IF ENHANCED FASTENING IS |
| | REQUIRED IN ZONES 2 AND OR 3, IDENTIFY EACH WITHIN THE |
| | PRODUCT APPROVAL, APPLY THEIR SHOP DRAWING STAMP OF |
| | APPROVAL BEFORE SUBMITTING TO THE BUILDING DEPARTMENT. |
| | WE DO NOT GUESS AT WHAT IS BEING INSTALLED, THAT IS WHY |
| | WE REQUEST THESE PRODUCTS AND PRESSURES TO BE |
| | IDENTIFIED. IT?S A LOT MORE COSTLY IN TIME AND MONEY TO |
| | FIND THE WRONG PRODUCT WAS ORDERED AND INSTALLED. |
| | THE WEST PALM BEACH ADMINISTRATIVE CODE 2017 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | 1ST ROUND OF COMMENTS. ROOFING: FOR ALL ROOFING |
| | PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND |
| | THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW |
| | THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING |
| | IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| | SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET |
| | AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |