| 2020-12-22 16:26:07 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100064 |
| | 12/22/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | UNRESOLVED COMMENTS FROM THE 1ST REVIEW ARE LISTED |
| | BELOW WITH ADDITIONAL NOTES IN CAP LETTERS. |
| | |
| | 2) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE |
| | WITH TABLE 403.3 FBC P. PLEASE NOTE THE OCCUPANT LOAD |
| | OF THE FACILITY IS BEING QUESTIONED BY THE BUILDING |
| | PLAN REVIEWER. AN INCREASED OCCUPANT LOAD COULD RESULT |
| | IN INCREASED FIXTURE REQUIREMENTS- TABLE 403.3 FBC P. |
| | THE PLUMBING FIXTURE CALCULATIONS ON SHEET A2.1 |
| | INDICATE UNISEX WATER CLOSETS ARE PROVIDED TO MEET THE |
| | REQUIREMENT OF TWO MALE AND TWO FEMALE WATER CLOSETS. |
| | BASED ON SECTIONS 403.1.1, 403.1.2, AND 403.2.1 FBC P |
| | THE PLUMBING FIXTURES AND RESTROOMS SHALL BE IDENTIFIED |
| | AS EITHER MALE OR FEMALE. THE EXCEPTION UNDER SECTION |
| | 403.2.1 APPLIES TO ASSEMBLY AND MERCANTILE OCCUPANCIES- |
| | SECTION 403.1.2 FBC P: FIXTURES LOCATED WITHIN FAMILY |
| | OR ASSISTED-USE TOILET AND BATHING ROOMS REQUIRED BY |
| | THE FLORIDA BUILDING CODE, ACCESSIBILITY ARE PERMITTED |
| | TO BE INCLUDED IN THE NUMBER OF REQUIRED FIXTURES FOR |
| | EITHER THE MALE OR FEMALE OCCUPANTS IN ASSEMBLY AND |
| | MERCANTILE OCCUPANCIES. SECTION 403.2.1 STATES FAMILY |
| | OR ASSISTED-USE TOILET FACILITIES SHALL NOT BE REQUIRED |
| | TO BE IDENTIFIED FOR EXCLUSIVE USE BY EITHER SEX AS |
| | REQUIRED BY SECTION 403.4- REQUIRED PUBLIC FACILITIES |
| | SHALL BE PROVIDED WITH SIGNS THAT DESIGNATE THE SEX. |
| | |
| | 3) SHEET A2.5: MISSING ACCESSIBLE PLUMBING FIXTURE |
| | DETAILS PER FBC ACC: |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. SHEETS A2.5 & P0.0: BASED |
| | ON THE 7' 1" DIMENSION ON THE ENTRANCE RESTROOM PLAN |
| | AND THE ACTUAL WIDTH OF THE SINK, IT APPEARS THAT THE |
| | CLEAR FLOOR SPACE OF THE WATER CLOSET WILL BE |
| | OVERLAPPING THE SINK- SEE SECTION 604.3.2 FBC ACC. |
| | |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. SHEET A2.5: PLEASE PROVIDE THE |
| | CLEAR FLOOR SPACE DIMENSIONS, AND REVISE THE PLAN IN |
| | RESPONSE RESPOND TO BUILDING COMMENT #7C. |
| | |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. SHEET A2.5- |
| | SHOW THE DIAMETERS. |
| | |
| | M) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 & |
| | 610.3.2. SHEET A2.5: THE END OF THE "L" SHALL BE 22 |
| | INCHES (560 MM) MINIMUM AND 23 INCHES MAXIMUM FROM THE |
| | MAIN SEAT WALL. |
| | |
| | N) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| | TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW |
| | THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE |
| | WITH SECTION 307.2 PROTRUSION LIMITS. SHEETS A2.0 & |
| | A3.3: THE DETAIL ON A3.3 APPEARS SHOWS NON-COMPLIANCE |
| | FOR PROTRUDING OBJECTS BECAUSE IT INDICATES A DRINKING |
| | FOUNTAIN WITH NO LEADING EDGES BELOW THE 27 IN. HEIGHT |
| | WHICH IS THE CANE DETECTION ZONE. |
| | |
| | L) REFER TO SECTIONS 305, 306, 308, AND 606 FBC ACC. |
| | AND PROVIDE THE CLEAR FLOOR SPACE APPROACH FOR THE |
| | BREAKROOM SINK, AND FRONT AND SIDE ELEVATION VIEWS |
| | SHOWING THE CORRECT HEIGHT OF THE SINK FROM THE |
| | FINISHED FLOOR. PLEASE NOTE THE HEIGHT OF THE BREAKROOM |
| | SINK IS INCORRECTLY SHOWN AT 3'0" ON SHEET A2.6. THE |
| | HEIGHT OF THE SINK WAS NOT CORRECTED. LAVATORIES AND |
| | SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER |
| | OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND- SECTION 606.2. |
| | |
| | 5) P0.0: PLEASE INCLUDE THE RECIRCULATION PUMP, THE |
| | MIXING VALVES, AND THE BACKFLOW PREVENTERS IN THE |
| | SCHEDULE- SECTIONS 607.1.2, 607.2.1, & 608.3 FBC P. |
| | MIXING VALVES AND BACKFLOW PREVENTERS WERE NOT INCLUDED |
| | IN THE SCHEDULE. PLEASE NOTE THE SPECIFICATIONS FOR THE |
| | MIXING VALVES AND BACKFLOW PREVENTERS MAY BE DEFERRED |
| | SUBMITTALS. |
| | |
| | 9) P2.1 & P.30: PLEASE LABEL THE HOT WATER RETURN (HWR) |
| | LINE IN THE DRAWINGS FOR CLARITY- SECTION 107.2.1 WPB. |
| | HWR NOT LABELED. |
| | 14) SHEETS A2.2 & P2.2 ROOF DRAINAGE- FBC P. |
| | |
| | G) SHOW HOW RAINWATER FROM THE CONCRETE CANOPIES |
| | INCLUDING TRIBUTARY RAINWATER FROM THE HIGH ROOFS WILL |
| | DRAIN TO AN APPROVED PLACE OF DISPOSAL- SECTION 1101.2. |
| | PLEASE CLARIFY IF GUTTERS WILL BE PROVIDED FOR THE EAST |
| | AND WEST ENTRANCE ROOF CANOPIES, OR IF THE RAINWATER |
| | WILL BE DRAINED AWAY FROM THE BUILDING INTO A BASIN OR |
| | PERMEABLE GROUND. |
| | |
| | NEW COMMENT: |
| | |
| | 1) P1 AND C07: PLEASE SHOW THE 4 INCH HORIZONTAL STORM |
| | DRAIN RUNNING ALONG THE WEST PERIMETER OF THE BUILDING- |
| | SEE SHEET P2.0. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |