| 2020-12-07 10:21:38 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100064 |
| | ADD: 1540 N. AUSTRALIAN AVE. / NEW BLDG. FOR HOUSING, |
| | COMMUNITY DEVELOPMENT) |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: |
| | E-MAIL: |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: MON. DEC. 07TH/2020 |
| | ACTION: DENIED |
| | |
| | 1-3) COMPLIED. |
| | 4) SHEET S1.0 SHOWS THE WIND DESIGN CRITERIA AND THE |
| | COMPONENTS AND CLADDING, THE EFFECTIVE WIND AREA CHARTS |
| | FOR ROOF ZONES 1,2,3, OVERHANG ZONE 2 AND OVERHANG ZONE |
| | 3 AS WELL AS WALL ZONES 4 & 5 WITH RESPECTIVE |
| | PRESSURES. |
| | |
| | 4A) COMPLIED. SPOKE WITH CHRIS PRUITT STRUCTURAL |
| | ENGINEER. WILL SEND ENG, PROGRAM IN PDF FORM, I WILL |
| | UPLOAD PROGRAM INTO PROJECT DOX DOCUMENT FOLDER FILE |
| | 12/18/2020. |
| | |
| | 4B) COMPLIED. 2017 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, SUN SHADES |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE INSULATION, CURBS AND ROOF TOP VENTILATORS |
| | |
| | 4C) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA |
| | ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4D & E) NOT APPLICABLE/ COMPLIED. |
| | |
| | |
| | 4F) 2ND REQUEST. RESPONSE INDICATES TO VIEW SHEET |
| | A3.0-3.1 A3.2, A6.1 AND A6.2 FOR INFORMATION REQUIRED. |
| | THE BUILDING DEPARTMENT REQUIRES ALL THE IMPORTANT |
| | INFORMATION TO BE FILED OUT WITHIN THE PRODUCT APPROVAL |
| | (LISTED BELOW IDENTIFY GLAZING, ANCHORS & MULLIONS) BY |
| | EITHER THE CONTRACTOR AND BEING REVIEWED BY THE |
| | DESIGNER OF RECORD AND APPLYING THEIR SHOP DRAWING OF |
| | APPROVAL, OR IN THE CASE WHERE NO CONTRACTOR HAS BEEN |
| | CHOSEN AND THE DESIGNER OF RECORD IS PICKING OUT THE |
| | PRODUCT APPROVALS, THEN THEY ARE THE ONES CHOOSING THE |
| | GLAZING, ANCHORS AND MULLIONS, IDENTIFY EACH WITHIN THE |
| | PRODUCT APPROVAL, APPLY THEIR SHOP DRAWING STAMP OF |
| | APPROVAL BEFORE SUBMITTING TO THE BUILDING DEPARTMENT. |
| | WE DO NOT GUESS AT WHAT IS BEING INSTALLED, THAT IS WHY |
| | WE REQUEST THESE PRODUCTS AND PRESSURES TO BE |
| | IDENTIFIED. IT?S A LOT MORE COSTLY IN TIME AND MONEY TO |
| | FIND THE WRONG PRODUCT WAS ORDERED AND INSTALLED. |
| | THE WEST PALM BEACH ADMINISTRATIVE CODE 2017 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1ST ROUND OF COMMENTS. IDENTIFY GLAZING/ ANCHORS/ |
| | MULLIONS. PLEASE IDENTIFY ON THE PRODUCT APPROVAL |
| | BEFORE SUBMITTING TO DESIGNER OF RECORD AND BEFORE |
| | SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS |
| | WITH GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & |
| | HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH IF |
| | UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2017 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURERS INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 4G) 2ND REQUEST.ROOFING. RESPONSE INDICATES TO VIEW |
| | SHEET A2.2. FOR INFORMATION REQUIRED. THE BUILDING |
| | DEPARTMENT REQUIRES ALL THE IMPORTANT INFORMATION TO BE |
| | FILED OUT WITHIN THE PRODUCT APPROVAL (LISTED BELOW FOR |
| | EACH ROOFING PRODUCT APPROVAL, SYSTEM AND SUB-SYSTEM BY |
| | EITHER THE CONTRACTOR AND BEING REVIEWED BY THE |
| | DESIGNER OF RECORD AND APPLYING THEIR SHOP DRAWING OF |
| | APPROVAL, OR IN THE CASE WHERE NO CONTRACTOR HAS BEEN |
| | CHOSEN AND THE DESIGNER OF RECORD IS PICKING OUT THE |
| | PRODUCT APPROVALS, THEN THEY ARE THE ONES CHOOSING THE |
| | SYSTEMS, SUB-SYSTEMS AND IF ENHANCED FASTENING IS |
| | REQUIRED IN ZONES 2 AND OR 3, IDENTIFY EACH WITHIN THE |
| | PRODUCT APPROVAL, APPLY THEIR SHOP DRAWING STAMP OF |
| | APPROVAL BEFORE SUBMITTING TO THE BUILDING DEPARTMENT. |
| | WE DO NOT GUESS AT WHAT IS BEING INSTALLED, THAT IS WHY |
| | WE REQUEST THESE PRODUCTS AND PRESSURES TO BE |
| | IDENTIFIED. IT?S A LOT MORE COSTLY IN TIME AND MONEY TO |
| | FIND THE WRONG PRODUCT WAS ORDERED AND INSTALLED. |
| | THE WEST PALM BEACH ADMINISTRATIVE CODE 2017 107.2.1. |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS SHALL |
| | BE SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1ST ROUND OF COMMENTS. ROOFING: FOR ALL ROOFING |
| | PRODUCTS PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND |
| | THEIR ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW |
| | THE PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING |
| | IS ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES |
| | SHALL BE INCREASED FOR BOTH INSULATION & THE BASE SHEET |
| | AS CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION |
| | STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 5) 2ND REQUEST, RESPONSE INDICATES THAT THE RTU WIND |
| | LOAD CALCULATIONS WILL BE PROVIDED BY THE STRUCTURAL |
| | ENGINEER. PLEASE NOTE NO SUCH WINDLAOD CALCULATIONS FOR |
| | THE RTU WERE SUBMITTED. |
| | 1ST ROUND OF COMMENTS. SHEET M4.1 AND DETAIL RTU |
| | TIE-DOWN DETAIL. THIS DETAIL INDICATES THE ANCHORING OF |
| | THE RTU CURB TO THE BAR JOIST BUT THE DETAIL DOES NOT |
| | INDICATE FOR WHAT WIND SPEED THESE CONNECTIONS ARE |
| | DESIGNED FOR OR THE TRIBUTARY AREA/ SURFACE AREA OF THE |
| | RTU THAT THIS CONNECTION WAS DESIGNED FOR? |
| | 2017 FBC-M- 301.15 WIND RESISTANCE. |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE |
| | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO |
| | RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH |
| | THE FLORIDA BUILDING CODE, BUILDING. |
| | FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| | PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| | BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| | ATTACHMENTS. |
| | LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP |
| | EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL |
| | MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY |
| | METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT |
| | EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY |
| | AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES. |
| | EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE |
| | OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS. |
| | |
| | 5A) COMPLIED. |
| | |
| | 5B)BUILDING PROVISO: THE STRUCTURAL SHEETS SHOW STEEL |
| | BEAMS, ROOF FRAMING, BAR JOIST AND METAL DECKING. THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. REPORTS SUBMITTED TO BUILDING INSPECTOR AT |
| | TIME OF FRAMING INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT |
| | 561-805-6666. |
| | |
| | 5C) 2ND REQUEST. THE RESPONSE INDICATES THAT AN |
| | ADDITIONAL DETAIL HAS BEEN ADDED TO THE PLAN, THERE IS |
| | NO SECTION OR DETAIL ADDED TO THIS AREA REFERENCING THE |
| | NEW DETAIL LOCATION. PLEASE NOTE SHEET S3.0 THE HOLE |
| | FOR THE ROOF ACCESS IS JUST FLOATING IN MID-AIR, NO |
| | FRAMING MEMBERS OR SECONDARY FRAMING MEMBERS AROUND THE |
| | ROOF ACCESS HOLE. 107/2/1/2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 5D)2ND REQUEST. THE RESPONSE SHEET STATES HE ROOF PLAN |
| | A2.2 WAS ADJUSTED TO SHOW A 30-INCH X 36-INCH |
| | BABCOCK-DAVIS ROOF HATCH. THE ONLY NOTE ON THIS PLAN |
| | IDENTIFIES THE ROOF HATCH AS RF9. |
| | ROOF TOP HATCHES/ ROOF ACCESS/ 2017 FBC-B 1011.12.2. IN |
| | BUILDINGS THAT DO NOT HAVE AN OCCUPIED ROOF SHALL BE |
| | PERMITTED TO BE A ROOF HATCH OR TRAP DOOR NOT LESS THAN |
| | 16 SQUARE FEET IN AREA AND HAVING A MINIMUM DIMENSION |
| | OF 2 FEET. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) SHEET A2.5 ENLARGED RESTROOM PLAN. |
| | 7A) SEMI-COMPLIED. THE SIDE WALL PANELS (DETAILS 5 & |
| | 15) BOTH INDICATE THE USE OF FRP PANELS BUT THE BACK |
| | WALL PANEL (4) DOES NOT STATE THE USE OF FRP PANELS. |
| | |
| | 1ST ROUND COMMENTS. THE ENTRANCE BATHROOM SHOWS EPOXY |
| | PANEL WALLS. PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATION FOR THIS PRODUCT. 2017 FBC-B 1210.2.2. |
| | WALLS & PARTITIONS. THIS COMMENT IS A RESULT OF THE |
| | BUILDING OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY |
| | PAINT IS NO LONGER CONSIDERED A SMOOTH HARD, |
| | NON-ABSORBENT SURFACE. |
| | WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 7B) COMPLIED. SHEET A2.5 DETAIL# 2 HCD RESTROOM FLOOR |
| | PLAN SHOWS THE 30X48 CLEAR FLOOR SPACE FOR THE LAV BUT |
| | THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER CLOSET IS |
| | NOT EVIDENT. |
| | CLEARANCES AT WATER CLOSETS. ACCESS. CODE 604.3 |
| | CLEARANCE. CLEARANCES AROUND THE WATER CLOSETS AND IN |
| | TOILET COMPARTMENTS SHALL COMPLY WITH 604.3. |
| | 604.3.1. SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM PERPENDICULAR FROM THE REAR |
| | WALL. NOTE THE MINIMUM BACK WALL MEASUREMENT SHOULD BE |
| | 7-FOOT 1 INCH. BACK WALL DIMENSION IS NOT GIVEN NOR THE |
| | DISTANCE OF THE LAV OFF THE SIDE WALL OR THE WATER |
| | CLOSET OF THE SIDE WALL. |
| | |
| | 7C) EXPLANATION. SORRY I DIDN?T CLARIFY WHAT I WAS |
| | LOOKING FOR IN THIS COMMENT. RESTROOMS AND BATHROOMS |
| | FOR SINGLE USER ROOMS CAN HAVE THE INSWING DOOR AND THE |
| | DOOR CAN SWING INTO THE CLEAR FLOOR AREAS IF THERE IS |
| | SUFFICIENT ROOM TO SHOW THE 30 X 48 CLEAR FLOOR SPACE |
| | BEYOND THE ARC OF THE DOOR. WHAT IS MISSING IS THE |
| | REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE ARC OF |
| | THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR ENTRANCE. |
| | SORRY I NEEDED TO GIVE CLARIFICATION. |
| | TOILET ROOM DOORS. 2017 FBC-ACCESSIBILITY CODE FIGURE |
| | 604.8.1.6 SHOWS AN OUTSWING DOOR. PLEASE ALSO REVIEW |
| | SECTION 603.2.3. DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACE OR CLEARANCES REQUIRED FOR ANY FIXTURE. |
| | DOORS SHALL BE PERMITTED TO SWING INTO THE REQUIRED |
| | TURNING SPACE. PLEASE SEE EXCEPTION 2. WHERE TOILET |
| | ROOMS ARE FOR INDIVIDUAL USE AND A CLEAR FLOORS SPACE |
| | COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND |
| | THE ARC OF THE DOOR SWING. WHAT IS MISSING IS THE |
| | REQUIRED 30X48 INCH CLEAR FLOOR SPACE BEYOND THE ARC OF |
| | THE DOOR. USUALLY AT A 45% ANGLE TO THE DOOR ENTRANCE. |
| | |
| | 7D) COMPLIED. |
| | |
| | 7E) 2ND REQUEST. SHEET A2-5 DETAILS 8, 11 & 13MISSING |
| | COMPLIANCE WITH TOILET PAPER DISPENSERS. 604.7. THE |
| | TOILET PAPER DISPENSER SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM TO 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. |
| | |
| | 7F) COMPLIED. |
| | |
| | 7G) COMPLIED |
| | . |
| | 7H)SEMI-COMPLIED. SEAT IS NOW SHOWN IN DETAIL # 1 & 4 |
| | BUT THERE IS NO DIMENSION FROM THE FRONT EDGE OF THE |
| | TRANSFER SEAT TO THE OUTSIDE WALL LINE OF THE SHOWER |
| | WHERE THE 30X48 INCH WHEELCHAIR SPACE BEGINS. SHOWER |
| | COMPARTMENT SEATS MUST EXTEND TO WITHIN 3 INCHES OF THE |
| | COMPARTMENT ENTRY. ACCESS. CODE 610.3. |
| | |
| | 7I) COMPLIED. |
| | |
| | 7J) COMPLIED. |
| | |
| | 8-9) COMPLIED. |
| | |
| | 10) IMPACT FEES - DIGITAL SUBMITTALS: PLANS WILL BE |
| | REVIEWED BY THE PBC IMPACT FEE OFFICE DIGITALLY VIA |
| | PROJECT DOX UPON NOTIFICATION BY THIS OFFICE. |
| | NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST FINAL |
| | FORM. YOU MAY COORDINATE WITH THE IMPACT FEE OFFICE AT |
| | (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL IMPACT |
| | FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME THE |
| | FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM CAN |
| | BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRAT |
| | ION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| | YOUR PROJECT OR EMAIL IT TO [email protected] |
| | . |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | WORKING HOURS ARE MON. ? WED. 8:00AM -UNTIL NOON. |
| | RETIRED/ PART TIME. |
| | |