| 2020-10-28 10:46:49 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100064 |
| | 10/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLACE A NOTE ON THE PLANS TO INDICATE THE WATER |
| | SERVICE BACKFLOW PREVENTER, AND THE IRRIGATION SYSTEM |
| | SHALL BE UNDER SEPARATE PERMIT- SECTION 107.2.1 WPB. |
| | |
| | 2) PROVIDE PLUMBING FIXTURE CALCULATIONS IN ACCORDANCE |
| | WITH TABLE 403.3 FBC P. PLEASE NOTE THE OCCUPANT LOAD |
| | OF THE FACILITY IS BEING QUESTIONED BY THE BUILDING |
| | PLAN REVIEWER. AN INCREASED OCCUPANT LOAD COULD RESULT |
| | IN INCREASED FIXTURE REQUIREMENTS- TABLE 403.3 FBC P. |
| | |
| | 3) SHEET A2.5: MISSING ACCESSIBLE PLUMBING FIXTURE |
| | DETAILS PER FBC ACC: |
| | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | WATER CLOSET- SECTION 604.3. |
| | B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| | LAVATORY- SECTION 606.2. |
| | C) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | SHOWER- SECTION 608.2.1 |
| | C) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL- |
| | SECTION 604.2. |
| | E) HEIGHT OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOOR- SECTION 604.4. PLEASE NOTE THE DRAWING |
| | INCORRECTLY SHOWS A 1?-3? HEIGHT TO THE WATER CLOSET |
| | RIM. |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4 |
| | G) LOCATION OF THE WATER CLOSET FLUSH CONTROL IS SHOWN |
| | ON THE WRONG SIDE IN THE SICKLE CELL BATHROOM ELEVATION |
| | - SECTION 604.6. |
| | H) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION 604.7. |
| | I) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| | 608.3.1 |
| | K) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| | SHOWER- SECTION 608.5.1. |
| | L) SHOWER SPRAY UNIT SPECIFICATIONS PER SECTION 608.6. |
| | M) LOCATION OF ACCESSIBLE SHOWER SEAT- SECTIONS 610.3 & |
| | 610.3.2. |
| | N) REFER TO SECTIONS 306, 307, AND 602 FBC ACC AND |
| | PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND |
| | ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT |
| | HEIGHTS, AND SPOUT LOCATIONS. SHOW THE REQUIRED 30 X 48 |
| | IN. CLEAR FLOOR SPACE FOR A FORWARD WHEELCHAIR APPROACH |
| | TO THE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW HOW |
| | THE LOCATIONS OF THE FOUNTAINS WILL BE IN COMPLIANCE |
| | WITH SECTION 307.2 PROTRUSION LIMITS. |
| | L) REFER TO SECTIONS 305, 306, 308, AND 606 FBC ACC. |
| | AND PROVIDE THE CLEAR FLOOR SPACE APPROACH FOR THE |
| | BREAKROOM SINK, AND FRONT AND SIDE ELEVATION VIEWS |
| | SHOWING THE CORRECT HEIGHT OF THE SINK FROM THE |
| | FINISHED FLOOR. PLEASE NOTE THE HEIGHT OF THE BREAKROOM |
| | SINK IS INCORRECTLY SHOWN AT 3'0" ON SHEET A2.6. |
| | |
| | 4) SHEET P0.0: PROVIDE THE EFFICIENCY RATING OF THE |
| | WATER HEATER- TABLE C404.3 FBC EC. |
| | |
| | 5) P0.0: PLEASE INCLUDE THE RECIRCULATION PUMP, THE |
| | MIXING VALVES, AND THE BACKFLOW PREVENTERS IN THE |
| | SCHEDULE- SECTIONS 607.1.2, 607.2.1, & 608.3 FBC P. |
| | |
| | 6) P0.0: PROVIDE A PLUMBING FIXTURE SCHEDULE INDICATING |
| | MAKES AND MODELS OF THE WATER CLOSETS, WATER CLOSET |
| | VALVES, LAVATORY SINKS AND FAUCETS, BREAKROOM SINK AND |
| | FAUCET, DISHWASHER, MOP SINK AND FAUCET, DRINKING |
| | FOUNTAIN, HOSE BIBS, AND SHOWER FAUCET AND SPRAY UNIT- |
| | SECTION 405 FBC P. |
| | |
| | 7) P2.0: THE DIAMETERS OF THE RWL PIPES NOT SHOWN- |
| | 1106.2 FBC P. |
| | |
| | 8) P2.0: THE HORIZONTAL STORM DRAIN PIPES REQUIRE |
| | CLEANOUTS AT 100 FT. INTERVALS- SECTIONS 1101.8 & |
| | 708.1.1 & , AND AT HORIZONTAL TO VERTICAL CHANGES OF |
| | DIRECTION- SECTION 708.1.4 FBC P. |
| | |
| | 9) P2.1 & P.30: PLEASE LABEL THE HOT WATER RETURN (HWR) |
| | LINE IN THE DRAWINGS FOR CLARITY- SECTION 107.2.1 WPB. |
| | |
| | 10) P2.1 & P3.0: A FULL OPEN SHUT OFF VALVE IS REQUIRED |
| | FOR AT THE BOTTOM OF THE CW RISER PIPE TO THE ROOF- |
| | SECTION 606.1(4) FBC P. |
| | |
| | 11) P2.1: SHOW THE HOT WATER LINE RUN TO THE BREAKROOM |
| | SINK, AND WATER LINES TO THE DISHWASHER- SECTIONS 409.2 |
| | & 607.1 FBC P. |
| | |
| | 12) P2.1 & P3.0: SHOW THE LOCATIONS OF REQUIRED WATER |
| | HAMMER ARRESTORS FOR SUPPLY LINES TO FIXTURES WITH |
| | QUICK CLOSING VALVES I.E. FLUSH VALVES, DRINKING |
| | FOUNTAINS, DISHWASHER, ICE MAKERS, COFFEE MACHINE ETC. |
| | SECTION 604.9 FBC P. |
| | |
| | 13) P3.0 & P4.1: SHOW THE LOCATION OF THE MASTER MIXING |
| | VALVE, AND THE REQUIRED MIXING VALVES AT THE |
| | LAVATORIES- SECTIONS 416.5 & 607.1.2 FBC P. PLEASE NOTE |
| | THE WATER HEATER SHOWS A MASTER MIXING BUT THE |
| | ISOMETRIC DOES NOT SHOW IT. |
| | |
| | 14) SHEETS A2.2 & P2.2 ROOF DRAINAGE- FBC P. |
| | |
| | A) PROVIDE PRIMARY ROOF DRAIN CALCULATIONS FOR SIZING |
| | THE ROOF DRAINS, VERTICAL LEADERS, AND HORIZONTAL DRAIN |
| | PIPES- SECTION 1105.2 & 1106.1. THE PLAN IS INDICATING |
| | CALCULATIONS FOR SECONDARY OR OVERFLOW CALCULATIONS BUT |
| | NOT THE PRIMARY ROOF DRAINS. PLEASE NOTE THE |
| | CALCULATIONS SHALL INCLUDE DRAINAGE FROM PARAPET WALLS- |
| | 1106.4. |
| | |
| | B) REFER TO SECTION 1105.2: THE CALCULATIONS SHALL BE |
| | BASED ON THE PUBLISHED ROOF DRAIN FLOW RATE, BASED ON |
| | THE HEAD OF WATER ABOVE THE ROOF DRAIN. THE FLOW RATE |
| | USED FOR SIZING THE STORM DRAINAGE PIPING SHALL BE |
| | BASED ON THE MAXIMUM ANTICIPATED PONDING AT THE ROOF |
| | DRAIN. |
| | |
| | C) REFER TO SECTION 1101.7 AND VERIFY COMPLIANCE: |
| | ROOFS SHALL BE DESIGNED FOR THE MAXIMUM POSSIBLE DEPTH |
| | OF WATER THAT WILL POND THEREON AS DETERMINED BY THE |
| | RELATIVE LEVELS OF ROOF DECK AND OVERFLOW WEIRS, |
| | SCUPPERS, EDGES OR SERVICEABLE DRAINS IN COMBINATION |
| | WITH THE DEFLECTED STRUCTURAL ELEMENTS. IN DETERMINING |
| | THE MAXIMUM POSSIBLE DEPTH OF WATER, ALL PRIMARY ROOF |
| | DRAINAGE MEANS SHALL BE ASSUMED TO BE BLOCKED. THE |
| | MAXIMUM POSSIBLE DEPTH OF WATER ON THE ROOF SHALL |
| | INCLUDE THE HEIGHT OF THE WATER REQUIRED ABOVE THE |
| | INLET OF THE SECONDARY ROOF DRAINAGE MEANS TO ACHIEVE |
| | THE REQUIRED FLOW RATE OF THE SECONDARY DRAINAGE MEANS |
| | TO ACCOMMODATE THE DESIGN RAINFALL RATE AS REQUIRED BY |
| | SECTION 1106. |
| | |
| | D) PROVIDE AN EQUIPMENT SCHEDULE FOR THE ROOF DRAINS- |
| | MAKE AND MODEL NUMBER, SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS, AND PROVIDE AN ENLARGED INSTALLATION |
| | DETAIL ON THE PLAN- SECTION 1105.1. |
| | |
| | E) SHEET A2.2: AT EACH LOW ROOF DRAIN IN THE DRAWING |
| | PLEASE SHOW THE ACCUMULATIVE SQ. FOOTAGE AND GPM FLOW |
| | FOR DRAINAGE FROM BOTH THE LOW AND HIGH ROOFS AND THE |
| | PARAPETS. REFER TO TABLES 1106.2 AND 1106.3 AND |
| | INDICATE THE SIZES OF THE VERTICAL LEADERS, AND THE |
| | SIZES AND SLOPES OF THE HORIZONTAL DRAINS. |
| | |
| | F) A2.2: SHOW THE LOCATIONS OF THE EMERGENCY SCUPPERS, |
| | PROVIDE SIZING CALCULATIONS AND AN ENLARGED DETAIL- |
| | SECTION 1108.3 FBC P AND SECTIONS 1503.4.1 & 1503.4.2 |
| | FBC B. |
| | |
| | G) SHOW HOW RAINWATER FROM THE CONCRETE CANOPIES |
| | INCLUDING TRIBUTARY RAINWATER FROM THE HIGH ROOFS WILL |
| | DRAIN TO AN APPROVED PLACE OF DISPOSAL- SECTION 1101.2. |
| | |
| | 15) SHOW COMPLIANCE WITH SECTION 310.3 FBC P FOR |
| | INTERIOR WALL FINISHES IN THE TOILET ROOMS AND AT THE |
| | MOP SINK LOCATION- SEE SECTION 1210.2.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |