| Date |
Text |
| 2020-10-30 15:17:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100064 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A CODE ANALYSIS FOR THIS PROJECT. FBC |
| | 107.2 |
| | |
| | 2) ACCORDING TO THE BUILDING REVIEWER, IT APPEARS THE |
| | OCCUPANT COUNT IS NOT PER THE BUILDING CODE. THE |
| | OUTSIDE AIR CALCULATIONS ARE BASED ON THE BUILDING |
| | OCCUPANT LOAD. WE CAN NOT DO THE OUTSIDE AIR |
| | CALCULATIONS UNTIL THE BUILDING OCCUPANT LOAD IS |
| | CONSISTENT WITH THE FBC. FBC M TABLE 403.3.1.1. |
| | |
| | 3) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION. FBC M |
| | TABLE 403.3.1.1 |
| | |
| | 4) PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC C402 |
| | |
| | 5) PLEASE PROVIDE CALCULATIONS FOR THE MECHANICAL |
| | SYSTEMS. FBC EC M403.2 |
| | |
| | 6) PLEASE SHOW ACCESS TO ROOF FOR THE RTU. FBC M 306.5 |
| | |
| | 7) PLEASE SHOW CLEARANCE AROUND RTU AND DISTANCE TO |
| | EDGE OF ROOF. FBC M 304.11 |
| | |
| | 8) PLEASE SHOW THAT THE INTAKE OPENING LOCATION FOR THE |
| | RTU MEETS FBC M 401.4 |
| | |
| | 9) PLEASE SHOW THAT THE EXHAUST TERMINATION LOCATIONS |
| | MEET FBC M 501.3.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | |