| Plan Review Notes For Permit 20100061 |
| Permit Number |
20100061 |
|
| Review Stop |
G |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-01-06 11:55:37 | 3RD REVIEW FBC-2017 RES. FUEL GAS | | | PERMIT- 20100061 | | | 1/6/2021 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE REVISED GAS RISER SHOWS - 3/4 IN. GALVANIZED | | | PIPE MAIN SUPPLY PIPE, A MAX 893,000 BTU LOAD, AND | | | SIZING TABLE 402.4(3) FBC FG. PLEASE NOTE BASED ON | | | TABLE 402.4(3) A 3/4 IN. WOULD BE LIMITED TO A MAXIMUM | | | 10 FT. TOTAL DEVELOPED LENGTH FOR THE MAX BTU LOAD- THE | | | RISER SHOWS A TOTAL DEVELOPED LENGTH OF 75 FT. IT | | | APPEARS THAT EITHER A MINIMUM 1-1/4 IN. MAIN SUPPLY | | | PIPE WILL HAVE TO INSTALLED, OR THE METER WILL HAVE TO | | | BE UPGRADED TO A 2 PSI SYSTEM- SECTION G2413.2 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|