| 2020-11-06 15:00:34 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100061 |
| | 11/6/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SUBMIT A GAS RISER DRAWING SHOWING THE COMPLETE GAS |
| | PIPING SYSTEM INCLUDING THE PIPING FOR THE GENERATOR, |
| | AND THE EXISTING PIPING INSTALLED UNDER PREVIOUS GAS |
| | PERMITS- 02040733 & 0800035- SECTIONS G2412.3 & G2412.4 |
| | FBC RES. PLEASE NOTE THAT BUILDING DEPARTMENT RECORDS |
| | FOR PERMIT 02040733 INDICATE AN EXISTING 587 BTUH |
| | SYSTEM WITH A TOTAL DEVELOPED LENGTH OF 75 FT. TO THE |
| | MOST REMOTE OUTLET. THE RISER SHOWS: WATER HEATER- 75 |
| | MBH, DRYER- 22 MBH, COOKTOP- 45 MBH, FUTURE BBQ- 45 |
| | MBH, POOL HEATER- 400 MBH. |
| | |
| | A) CORRECT THE TOTAL LOAD AND THE INDIVIDUAL LOADS OF |
| | THE SYSTEM- SECTIONS G2412.3, G2412.4, & G2413.2 FBC |
| | RES. PLEASE NOTE THAT THE ? IN. MAIN RISER PIPE IS |
| | UNDERSIZED TO SUPPLY THE TOTAL LOAD OF 914,000 BTUH AT |
| | TOTAL DEVELOPED LENGTH OF 75,000 USING TABLE 402.4(3) |
| | SHOWN ON THE PLAN. |
| | |
| | B) PROVIDE THE TOTAL LENGTH DEVELOPED LENGTH OF THE |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET, AND |
| | THE INDIVIDUAL BRANCH LENGTHS- SECTIONS G2413.4.1 AND |
| | G2413.4.2 FBC RES. |
| | |
| | C) SHOW THE LOCATIONS OF SHUT OFF VALVES AND PIPE |
| | UNIONS- SECTIONS G2420.5 & G2422.1.4. |
| | |
| | D) SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE |
| | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, SPRING DATA, AND ORIFICE SIZE- SECTIONS |
| | G2421.1 & G2421.2 FBC RES. |
| | |
| | 2) PLEASE CORRECT THE NOTE ON THE SURVEY TO INDICATE |
| | THE MINIMUM 10 FT. CLEARANCE TO MECHANICAL AND GRAVITY |
| | AIR INTAKES INTO THE BUILDING- SECTION R303.5.1 RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |