| 2020-10-16 11:55:38 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | 1) FBC B 107.2.1, THE SUBMITTED INFORMATION IS NOT |
| | CLEAR. PLEASE PROVIDE CLARIFICATION OF USE OF THE |
| | PROPOSED CONSTRUCTION OF KNEE WALLS IDENTIFIED AS A02A, |
| | A02B, A02C & A07. |
| | |
| | |
| | 2) FBC B 107.2.1, PLEASE PROVIDE MORE DETAILED |
| | INFORMATION FOR THE FLOOR PATCHING AND NEW FLOORING |
| | INCLUDING: |
| | |
| | TEST REPORTS ARE REQUIRED - MANUFACTURER SPEC SHEETS |
| | ARE NOT ACCEPTABLE DUE TO DISCREPANCIES BETWEEN SPEC |
| | SHEETS/BROCHURES AND TEST REPORTS FOR SOME |
| | MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER |
| | SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY |
| | RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | |
| | |