| 2020-10-07 15:39:00 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100019 |
| | 10/7/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) GAS RISER DRAWING: RECORDS RESEARCH FOR 235 EDMOR |
| | SHOWS A 400,000 BTUH POOL HEATER ISSUED UNDER |
| | PERMIT-12020716. PLEASE PROVIDE A COMPLETE RISER |
| | DRAWING THAT INCLUDES THE BRANCH LINE TO THE POOL |
| | HEATER, AND THE BRANCH LINE TO THE INTERIOR APPLIANCES. |
| | SHOW THE TOTAL LENGTHS OF THE BRANCHES, AND THE TOTAL |
| | DEVELOPED LENGTH OF THE SYSTEM FROM THE METER TO THE |
| | MOST REMOTE OUTLET. YOU ARE INDICATING THE EXISTING |
| | LOAD AT 900,000 BTUH. SHOW ON THE RISER THE INDIVIDUAL |
| | APPLIANCE LOCATIONS AND THEIR INDIVIDUAL LOADS- REFER |
| | TO SECTIONS G2412.3, G2412.4, G2413.1, & G2413.2 FBC |
| | RES. FUEL GAS. |
| | |
| | A) SHOW THE DELIVERY PRESSURE AT THE OUTLET OF THE NEW |
| | REGULATOR, AND THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF |
| | EITHER SIDE OF THE REGULATOR- SECTIONS G2421.1 & |
| | G2421.2(7). |
| | |
| | B) INDICATE THE MAKE AND MODEL OF THE REGULATOR ON THE |
| | RISER AND MARK OR HIGHLIGHT THE SPECS TO SHOW THE |
| | SELECTED MODEL, THE MAX INLET AND OUTLET SIZE AND |
| | PRESSURES, AND ORIFICE SIZE. |
| | |
| | 2) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | PLEASE INCLUDE A TITLE BLOCK ON THE DRAWING THAT |
| | INCLUDES CONTRACTOR OR COMPANY NAME AND LICENSE NUMBER. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |