| 2020-11-18 12:37:45 | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100012 |
| | 11/18/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW |
| | WITH ADDITIONAL NOTES. |
| | |
| | 1) FAILED. SURVEY: INDICATE THE REQUIRED 10 FT. |
| | CLEARANCE DISTANCE FOR THE UG TANK TO THE DRIVEWAY- |
| | SECTION 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED |
| | WITH 10 FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR |
| | VEHICLE PROTECTION SHALL BE PROVIDED. THE CLEARANCE |
| | DISTANCE FROM THE UG TANK TO THE DRIVEWAY NOT SHOWN. |
| | INSTALLATION DETAILS FOR DOME AND COVER NOT PROVIDED. |
| | |
| | 3) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| | BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| | IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. TANK SPECS NOT SUBMITTED. |
| | |
| | 4) FAILED. PROVIDE LP TANK INSTALLATION DETAILS AS |
| | REQUIRED BY NFPA 58: |
| | |
| | A) FAILED. ENGINEERING FOR ANCHORING THE TANK TO |
| | PREVENT FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- |
| | SECTION 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE |
| | ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING |
| | BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF |
| | ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE |
| | SLEEVES FOR THE CABLES OR STRAPS. PLEASE PROVIDE A |
| | COMPLETE DETAIL THAT INCLUDES THE ATTACHMENT OF THE |
| | DOME AND COVER. |
| | |
| | B) FAILED. SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1 |
| | (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT |
| | WILL BE TESTED- SECTION 6.17.1. DETAIL FOR ANODE BAG |
| | INSTALLATION NOT PROVIDED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |