| 2020-10-26 14:06:41 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100012 |
| | 10/26/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SURVEY: INDICATE THE REQUIRED 10 FT. CLEARANCE |
| | DISTANCE FOR THE UG TANK TO THE DRIVEWAY- SECTION |
| | 6.6.6.1(B) & (C) NFPA 58-14. TANKS INSTALLED WITH 10 |
| | FT. SHALL BE INSTALLED 18 IN. BELOW GRADE OR VEHICLE |
| | PROTECTION SHALL BE PROVIDED. |
| | |
| | 2) SURVEY: CORRECT THE 5 FT. GENERATOR EXHAUST |
| | CLEARANCE TO OPENINGS INTO THE BUILDING. A 10 FT. |
| | CLEARANCE IS REQUIRED TO MECHANICAL AND GRAVITY AIR |
| | INTAKES INTO THE BUILDING PER SECTION R303.5.1 FBC RES. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | 500-GALLON UG LP TANK SHOWING THE TANK AND DOME HAVE |
| | BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED) |
| | IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE |
| | REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN |
| | SECTION 5.2.1.1 NFPA 58. |
| | |
| | 4) PROVIDE LP TANK INSTALLATION DETAILS AS REQUIRED BY |
| | NFPA 58: |
| | A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| | FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| | 6.6.1.6. PLEASE INCLUDE A FRONT AND SIDE ELEVATION VIEW |
| | THAT SHOWS THE BURIAL DEPTH, ANCHORING BASE MATERIAL, |
| | AND THE TYPES, SIZES, AND NUMBERS OF ANCHORS, CABLES OR |
| | STRAPS, AND THE TYPE OF PROTECTIVE SLEEVES FOR THE |
| | CABLES OR STRAPS. |
| | B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & 6.6.6.1 |
| | (1) NFPA 58. INDICATE THE TYPE OF PROTECTION AND HOW IT |
| | WILL BE TESTED- SECTION 6.17.1 |
| | |
| | 5) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |