| 2020-10-05 13:42:47 | 10/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED |
| | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 105.1. |
| | |
| | 2. SHEET 1, 2, 3, AND 4 SHOWS A GAS STOVE AND 7 |
| | ELECTRICAL SHEETS SHOWS A COOK TO PLEASE CLARIFY WHICH |
| | ONE WILL BE USED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. SHEET 2 SHOWS PLUMBING RUNNING ON THE FOOTER PLEASE |
| | SHOW IT OUT OF THE FOOTER FOR CLARITY IN THE FIELD PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE SHOW THE SOURCE OF HOT WATER AS ON SHEET 9 |
| | FOR HVAC SHOWS THE HEATER IN THE LAUNDRY ROOM WITH NO |
| | LAUNDRY TRAY SHOWN. IF THE HEATER IS IN THE LAUNDRY |
| | ROOM, PLEASE SHOW DRAINAGE TO THE OUTSIDE OF THE |
| | STRUCTURE WITH RODENT PROOFING PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |