| 2020-10-08 11:52:02 | 2ND REVIEW FBC-2017 RES. |
| | PERMIT- 20091341 |
| | 10/8/2020 |
| | |
| | CODES IN EFFECT |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) CONCERNING THE GAS LINE RECONNECT: A) SHOW THE |
| | LOCATION OF THE NEW REGULATOR, INDICATE THE SELECTED |
| | MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND THE |
| | REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE |
| | REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS |
| | G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS |
| | ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE |
| | INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES, |
| | AND ORIFICE SIZES. PLEASE NIOTE THE GENERATOR SPECS |
| | INDICATE INPUT PRERSSURE OF 3.5- 7 IN.W.C. |
| | |
| | 2)THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS |
| | RISER DRAWING SHALL PROVIDE HIS/HER TITLE BLOCK AND |
| | SIGNATURE ON IT- SECTION 107.2.1 WPB, AND FLORIDA |
| | STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |