Plan Review Notes
Plan Review Notes For Permit 20091341
Permit Number 20091341
Review Stop G
Sequence Number 3
Notes
Date Text
2020-10-08 11:52:022ND REVIEW FBC-2017 RES.
 PERMIT- 20091341
 10/8/2020
  
 CODES IN EFFECT
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) CONCERNING THE GAS LINE RECONNECT: A) SHOW THE
 LOCATION OF THE NEW REGULATOR, INDICATE THE SELECTED
 MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND THE
 REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE
 REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS
 G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS
 ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE
 INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES,
 AND ORIFICE SIZES. PLEASE NIOTE THE GENERATOR SPECS
 INDICATE INPUT PRERSSURE OF 3.5- 7 IN.W.C.
  
 2)THE CONTRACTOR OR QUALIFIER WHO PREPARED THE GAS
 RISER DRAWING SHALL PROVIDE HIS/HER TITLE BLOCK AND
 SIGNATURE ON IT- SECTION 107.2.1 WPB, AND FLORIDA
 STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  