Plan Review Notes
Plan Review Notes For Permit 20091341
Permit Number 20091341
Review Stop G
Sequence Number 2
Notes
Date Text
2020-10-06 14:28:212ND REVIEW FBC-2017 RES.
 PERMIT- 20091341
 10/6/2020
  
 CODES IN EFFECT
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW STILL EXIST.
 NO CORRECTED PLANS OR COMMENT RESPONSES WERE UPLOADED
 FOR REVIEW.
  
 1) IT APPEARS THERE ARE TWO SEPARATE GENERATORS ON THE
 PROPERTY HOWEVER THE APPROVED PLANS UNDER THE PRIMARY
 PERMIT- 20080725 YOU HAVE LISTED ON YOUR APPLICATION
 SHOW A NEW (NOT A REPLACEMENT) 22 KW 327,000 BTUH
 GENERATOR LOCATED ON THE SOUTH SIDE OF THE HOUSE. THE
 SURVEY DRAWING YOU HAVE SUBMITTED INDICATES REPLACING A
 500,000 BTUH GENERATOR ON THE WEST SIDE OF THE
 PROPERTY. PLEASE NOTE THERE WERE NO GAS PIPING PLANS
 SUBMITTED AND NO GAS PERMIT ISSUED FOR THE GENERATOR
 UNDER PERMIT- 20080275, HOWEVER GAS PERMIT 07120106 WAS
 ISSUED FOR A 630,000 BTUH GENERATOR ON 02/04/2008. THIS
 GENERATOR APPEARS TO BE THE ONE THAT IS BEING REPLACED,
 HOWEVER THERE IS NO PERMIT ON FILE FOR REPLACEMENT OF
 THAT GENERATOR AND THE $1000.00 JOB VALUE LISTED ON
 YOUR APPLICATION IS A VERY LOW VALUE IF YOU ARE ALSO
 SUPPLYING THE GENERATOR. PLEASE PROVIDE A COPY OF A
 SIGNED CONTRACT AND/OR ESTIMATES OR INVOICES TO VERIFY
 THE TOTAL JOB COST INCLUDING LABOR, MATERIALS, THE
 GENERATOR, DESIGN FEES, AND SITE WORK- SECTION 109.3
 WPB.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE 500,000
 BTUH GENERATOR- SECTION 107.2.1 WPB. THE SPECS SHALL BE
 MARKED UP TO SHOW THE BTUH CAPACITY OF THE GENERATOR,
 AND REQUIRED NATURAL GAS INPUT PRESSURE.
  
 3) GAS RISER:
  
 A) SHOW THE LOCATION OF THE NEW REGULATOR, INDICATE THE
 SELECTED MAKE AND MODEL, SHOW THE OUTLET PRESSURE, AND
 THE REQUIRED PIPE UNIONS WITHIN 1 FT. OF EITHER SIDE OF
 THE REGULATOR IF CONNECTED TO RIGID PIPING. SECTIONS
 G2421.1 & G2421.2 FBC RES. PLEASE NOTE REGULATOR SPECS
 ONSITE SHALL BE MARKED UP OR HIGHLIGHTED TO INDICATE
 INTERIOR OR EXTERIOR USE, INLET AND OUTLET PRESSURES,
 AND ORIFICE SIZES.
  
 B) SHOW THE LOCATION OF THE DRIP LEG- SECTION G2419.2
 FBC RES.
  
 C) INDICATE A TRACER WIRE WILL BE INSTALLED ADJACENT TO
 THE UG PE PIPING- SECTION G2415.17.3.
  
 3) SURVEY: SHOW THE GENERATOR CLEARANCES TO THE
 ADJACENT PROPERTY LINES AND THE BUILDING, AND
 MECHANICAL AIR INTAKES AND OPERABLE OPENINGS INTO THE
 BUILDING- SEC. 4.1.4 NFPA 37 AND SECTION R303.5.1 FBC
 RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  