| Plan Review Notes For Permit 20091290 |
| Permit Number |
20091290 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-11-04 15:43:14 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE EXPOSURE CATEGORY IS STILL SPECIFIED AS C ON | | | SHEET T-1 IN THE LOADING CRITERIA. THE DRAWINGS SPECIFY | | | THAT THE EXPOSURE CATEGORY IS C. THIS PROJECT IS | | | LOCATED IN EXPOSURE CATEGORY D. FBC 1609.4 | | | | | | 2) THIS ITEM HAS NOT BEEN FULLY ADDRESSED. ON SHEET | | | C-5, SPECIFY THE REQUIRED EMBED DEPTH AND THE ANCHOR | | | SPACING REQUIRED FOR ATTACHING THE THE UNISTRUT TO THE | | | WALL OF THE BUILDING. CITY AMENDMENTS FBC 107.2.1 | | | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. |
|