| Plan Review Notes For Permit 20091290 |
| Permit Number |
20091290 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-14 14:00:43 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE APPURTENANCE MOUNT MODIFICATION ANALYSIS STATES | | | THAT IT WAS DONE IN ACCORDANCE WITH THE 2018 | | | INTERNATIONAL BUILDING CODE. THE 2018 IBC HAS NOT BE | | | ADOPTED BY THE STATE OF FLORIDA AT THIS TIME. THE | | | CURRENT CODE IS THE 2017 FLORIDA BUILDING CODE. PLEASE | | | REVISE. | | | | | | 2) THE DRAWINGS SPECIFY THAT THE EXPOSURE CATEGORY IS | | | C. THIS PROJECT IS LOCATED IN EXPOSURE CATEGORY D. FBC | | | 1609.4 | | | | | | 3) ON DRAWING SHEET C-3, THE RRUS UNITS ARE SHOWN AS | | | BEING RELOCATED TO UNISTRUT ATTACHED TO THE WALL OF THE | | | BUILDING. PROVIDE ATTACHMENT DETAILS WITH THE REQUIRED | | | NUMBER AND TYPES OF FASTENERS FOR ATTACHING THE | | | UNISTRUT AND MOUNTING THE BOXES TO THE UNISTRUT. CITY | | | AMENDMENTS FBC 107.2.1 | | | | | | 4) THE ENGINEER THAT DIGITALLY SIGNED AND SEALED THE | | | APPURTENANCE MOUNT MODIFICATION ANALYSIS, SELF | | | CERTIFIED HIS SIGNATURE. THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS REQUIRES ENGINEERS TO HAVE A | | | THIRD PARTY CERTIFICATION OF THEIR DIGITAL SIGNATURES. | | | | | | 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. |
|