| 2020-11-24 10:26:48 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20091250 |
| | 11/24/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A1.1 & A3.1: AS PREVIOUSLY NOTED THE DRINKING |
| | FOUNTAIN IS PROTRUDING INTO THE INTO THE CIRCULATION |
| | PATH WHICH IS NOT ALLOWED PER SECTION 307.2 FBC ACC. |
| | |
| | 2) PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | DRINKING FOUNTAIN INDICATING THE MAKE AND MODEL OF THE |
| | UNIT- SECTION 410.1 FBC P. |
| | |
| | 3) SHEET MP: THE DRINKING FOUNTAIN DRAIN CANNOT CONNECT |
| | TO THE HORIZONTAL WET VENT OF THE BATHROOM FIXTURES PER |
| | SECTION 912.1 FBC P. THE DRAIN SHALL CONNECT DOWNSTREAM |
| | OF THE WET VENT AND BE INDIVIDUALLY VENTED. |
| | |
| | 4) MP: PROVIDE A WATER HAMMER ARRESTOR FOR THE WATER |
| | SUPPLY LINE TO THE DRINKING FOUNTAIN- SECTION 604.9 FBC |
| | P. |
| | |
| | 5) 3RD REQUEST FOR A SLAB REPAIR FOR THE NEW PLUMBING |
| | DRAIN INSTALLATION - SECTION 107.2.1 WPB. |
| | |
| | 6) 3RD REQUEST FOR A PLUMBING SUB-PERMIT APPLICATION- |
| | SECTION 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |