2020-11-17 09:13:182ND REVIEW FBC-2017 PLUMBING
 PERMIT- 20091250
 11/17/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
 THE NEW PLAN SHEET MP1 WAS NOT UPLOADED FOR REVIEW. THE
 COMMENTS FROM THE 1ST REVIEW LISTED BELOW ARE MARKED AS
 PASSED OR FAILED. SOME NOTES HAVE BEEN ADDED TO FAILED
 COMMENTS.
  
 1) FAILED- NO PLANS SUBMITTED. REFER TO SECTION
 107.3.5.1.1 AMENDMENTS TO THE FBC-17 AND PROVIDE
 PLUMBING PLANS INCLUDING:
 A) FAILED. SCOPE OF WORK OUTLINE.
 B) FAILED. SANITARY AND WATER RISER DRAWINGS FOR
 INSTALLATION OF THE NEW DRINKING FOUNTAINS.
 C) FAILED. PLUMBING FIXTURE CALCULATIONS- TABLE 403.3
 FBC P. INDICATE THE REQUIRED AND PROVIDED NUMBER OF
 FIXTURES PER THE TABLE.
 D) FAILED. REFER TO SECTIONS 306, 307, AND 602 FBC ACC
 AND PROVIDE DRINKING FOUNTAIN INSTALLATION DETAILS AND
 ELEVATION VIEWS SHOWING KNEE AND TOE CLEARANCES, SPOUT
 HEIGHTS, AND SPOUT LOCATIONS. INDICATE HOW THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2-
 PROTRUDING OBJECTS INTO THE CIRCULATION PATH. THE
 DETAIL ON SHEET A3.1 IS INCOMPLETE- REFER TO FIGURES
 306.2, 307.2, & 602.5 FBC ACC. IT APPEARS A
 BARRIER-FREE TYPE DRINKING FOUNTAIN IS PROPOSED WHICH
 NEEDS TO BE INSTALLED IN A RECESSED NICHE TO BE IN
 COMPLIANCE WITH SECTION 307.2 FOR PROTRUDING OBJECTS
 INTO THE CIRCULATION PATH.
  
 2) FAILED. PROVIDE A SLAB REPAIR DETAIL- SECTION
 107.2.1 WPB.
  
 3) PASSED. SHEET A1.1: LABEL THE TOILET ROOMS 131 AND
 132 AS EITHER NEW OR EXISTING- SECTION 107.2.1 WPB.
  
 4) FAILED. PROVIDE A PLUMBING SUB-PERMIT APPLICATION-
 SECTION 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  