Plan Review Notes
Plan Review Notes For Permit 20091250
Permit Number 20091250
Review Stop E
Sequence Number 2
Notes
Date Text
2020-11-23 08:26:02ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED,
  
 PLAN REVIEW COMMENT RESPONSES SIGNED MAKES REFERENCE TO
 A REVISED EP-1 SUBMITTED ADDRESING THE COMMENTS FROM
 REVIEW NO. 1. HOWEVER, IT SEEMS THAT THE REVISED EP-1
 HAS NOT BEEN UPLOADED YET. THE PREVIOUS COMMENTS STILL
 NEED TO BE ADDRESSED.
  
 PREVIOUS COMMENTS BELOW:
  
 AHUS AND HPS:
  
 1) INDICATE LOCATION OF EQUIPMENT AND DISCONNECTING
 MEANS ON ELECTRICAL DRAWINGS AND CIRCUIT NUMBER AND
 PANEL.
 2) SPECIFY SIZE OF CONDUCTORS FEEDING EACH UNIT.
 INCLUDE GROUNDING EQUIPMENT CONDUCTOR (NEC 440)
 3) PROVIDE REQUIRED 125-VOLT, SINGLE-PHASE, 15 OR 20
 AMPS RATED RECEPTACLE WITHIN 25 FEET OF EACH UNIT AS
 PER NEC 210-63. IF UNITS ARE LOCATED IN ROOFTOPS
 RECEPTABLE MUST BE GFCI TYPE (NEC 210-8 B(3)
  
 PANELS C AND D:
  
 4) INDICATE LOCATION ON ELECTRICAL DRAWINGS
  
 SIGNATURE:
  
 5) SEE SIGNATURE COMMENTS FOR ALL DRAWINGS (DIGITAL
 SIGNATURE IS REQUIRED).
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED
 PLAN IS NOT CONSIDERED AN ORIGINAL.