| 2020-11-23 08:26:02 | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, |
| | |
| | PLAN REVIEW COMMENT RESPONSES SIGNED MAKES REFERENCE TO |
| | A REVISED EP-1 SUBMITTED ADDRESING THE COMMENTS FROM |
| | REVIEW NO. 1. HOWEVER, IT SEEMS THAT THE REVISED EP-1 |
| | HAS NOT BEEN UPLOADED YET. THE PREVIOUS COMMENTS STILL |
| | NEED TO BE ADDRESSED. |
| | |
| | PREVIOUS COMMENTS BELOW: |
| | |
| | AHUS AND HPS: |
| | |
| | 1) INDICATE LOCATION OF EQUIPMENT AND DISCONNECTING |
| | MEANS ON ELECTRICAL DRAWINGS AND CIRCUIT NUMBER AND |
| | PANEL. |
| | 2) SPECIFY SIZE OF CONDUCTORS FEEDING EACH UNIT. |
| | INCLUDE GROUNDING EQUIPMENT CONDUCTOR (NEC 440) |
| | 3) PROVIDE REQUIRED 125-VOLT, SINGLE-PHASE, 15 OR 20 |
| | AMPS RATED RECEPTACLE WITHIN 25 FEET OF EACH UNIT AS |
| | PER NEC 210-63. IF UNITS ARE LOCATED IN ROOFTOPS |
| | RECEPTABLE MUST BE GFCI TYPE (NEC 210-8 B(3) |
| | |
| | PANELS C AND D: |
| | |
| | 4) INDICATE LOCATION ON ELECTRICAL DRAWINGS |
| | |
| | SIGNATURE: |
| | |
| | 5) SEE SIGNATURE COMMENTS FOR ALL DRAWINGS (DIGITAL |
| | SIGNATURE IS REQUIRED). |
| | |
| | FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR |
| | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED |
| | PLAN IS NOT CONSIDERED AN ORIGINAL. |