| 2020-10-16 14:48:10 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20091250 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE OUTSIDE AIR CALCULATIONS. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 2) PLEASE PROVIDE AN OCCUPANT LOAD FOR THIS PROJECT. |
| | FBC M TABLE 403.3.1.1 |
| | |
| | 3) PLEASE PROVIDE A SCOPE OF WORK FOR THE MECHANICAL |
| | SYSTEMS. FBC 107.2.1 |
| | |
| | 4) PLEASE PROVIDE A DEMO SHEET FOR THE MECHANICAL |
| | SYSTEMS. FBC 107.2.1 |
| | |
| | 5) IF THIS IS ALL NEW UNITS, PLEASE PROVIDE |
| | CALCULATIONS FOR HEATING AND COOLING LOADS. FBC EC |
| | C403.2.1 |
| | |
| | 6) PLEASE SHOW THE LOCATION OF THE OUTSIDE AIR DUCT |
| | TERMINATIONS. PROVIDE A ROOF DETAIL SHEET TO VERIFY ALL |
| | CLEARANCES ARE MET. FBC M 401.4 |
| | |
| | 7) PLEASE SHOW THE TERMINATION LOCATION FOR THE |
| | BATHROOM EXHAUST FANS. FBC M 501.3 |
| | |
| | 8) PLEASE SHOW THE CFM?S THAT AHU-3 IS SUPPLYING TO THE |
| | RECEPTION AREA. FBC107.2.1 |
| | |
| | 9) PLEASE SHOW THE LOCATION OF THE CONDENSING UNITS. |
| | FBC 107.2.1 |
| | |
| | 10) PLEASE SHOW WHERE THE CONDENSATION FOR EACH OF THE |
| | AHU?S WILL BE DISPOSED. THERE IS NO PLUMBING SHEET |
| | ATTACHED TO THIS PROJECT. FBC M 307.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |