| Plan Review Notes For Permit 20091250 |
| Permit Number |
20091250 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-29 15:23:18 | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, | | | SEE COMMENTS BELOW | | | | | | AHUS AND HPS: | | | | | | 1) INDICATE LOCATION OF EQUIPMENT AND DISCONNECTING | | | MEANS ON ELECTRICAL DRAWINGS AND CIRCUIT NUMBER AND | | | PANEL. | | | 2) SPECIFY SIZE OF CONDUCTORS FEEDING EACH UNIT. | | | INCLUDE GROUNDING EQUIPMENT CONDUCTOR (NEC 440) | | | 3) PROVIDE REQUIRED 125-VOLT, SINGLE-PHASE, 15 OR 20 | | | AMPS RATED RECEPTACLE WITHIN 25 FEET OF EACH UNIT AS | | | PER NEC 210-63. IF UNITS ARE LOCATED IN ROOFTOPS | | | RECEPTABLE MUST BE GFCI TYPE (NEC 210-8 B(3) | | | | | | PANELS C AND D: | | | | | | 4) INDICATE LOCATION ON ELECTRICAL DRAWINGS | | | | | | SIGNATURE: | | | | | | 5) SEE SIGNATURE COMMENTS FOR ALL DRAWINGS (DIGITAL | | | SIGNATURE IS REQUIRED). | | | | | | FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED | | | PLAN IS NOT CONSIDERED AN ORIGINAL. |
|